Overview of Analog Units
Unit
Model
Baud rate setting
Moving average
Off-wire detection
Scaling, offset compensation, peak/
bottom hold, top/valley hold, rate of
change operations, comparator,
user adjustment (maintenance func-
tion), cumulative counter (mainte-
nance function), last maintenance
date (maintenance function)
Analog Output Units
Unit
Model
Analog points
Output signal range
Conversion time
DA conversion data
Resolution
Unit power supply
Communications power sup-
ply current consumption
Overall accuracy
25°C
−10 to
55°C
Data allocated in I/O
Output range switching
Node address setting
Baud rate setting
Communications error output
Scaling, user adjustment
(maintenance function), cumu-
lative counter (maintenance
function), last maintenance
date (maintenance function)
Note
GRT1 Series
GRT1-AD2
No setting required.
Supported. (Set using Setting Tool.)
Supported.
Supported. (Set using Setting Tool.)
GRT1 Series
GRT1-DA2V
(Voltage Output)
2 outputs
0 to 5 V, 1 to 5 V, 0 to 10 V,
–10 to 10 V
2 ms/2 points
0 to 5 V, 1 to 5 V, 0 to
10 V: 0000 to 1770 hex
–10 to 10 V: F448 to 0BB8
hex
Note Two's complement
1/6,000 (full scale)
Supplied by slice bus.
None
±
0.4% FS
±
0.8% FS
Only Analog output values for 2 outputs
Set using the DIP switch or Setting Tool.
No setting required.
No setting required.
Set using the Setting Tool.
Supported. (Set using the Setting Tool.)
In 0- to 20-mA mode, accuracy cannot be ensured at 0.2 mA or less.
DRT2-AD04
Automatically detected: Uses baud
rate set for Master Unit.
Supported. (Set using DeviceNet Con-
figurator.)
Supported. (Set using DeviceNet Con-
figurator.)
GRT1-DA2C
(Current Output)
0 to 20 mA, 4 to 20 mA
0 to 20 mA, 40 to 20 mA:
0000 to 1770 hex
Note Two's Complement
±
0.4% FS (See note.)
±
0.8% FS (See note.)
Section 5-1
DRT2 Series
DRT2 Series
DRT2-DA02
0 to 5 V, 1 to 5 V, 0 to 10 V, –10 to
10 V, 0 to 20 mA, 4 to 20 mA
0 to 5 V, 1 to 5 V, 0 to 10 V, 0 to
20 mA, 4 to 20 mA: 0000 to 1770
hex
–10 to 10 V: F448 to 0BB8 hex
Note Two's complement
Supplied by communications
power supply.
120 mA max.
Voltage output: ±0.3% FS, Cur-
rent output: ±0.4% FS
Voltage output: ±0.6% FS, Cur-
rent output: ±0.8% FS
Default: Analog output values for
2 points
The DeviceNet Configurator can
be used to allocate Generic Sta-
tus Flags.
Set using the DIP switch or the
DeviceNet Configurator.
Set using the rotary switches or
the DeviceNet Configurator.
Automatically detected: Uses the
baud rate set for the Master Unit.
Set using the DeviceNet Configu-
rator.
Supported. (Set using the
DeviceNet Configurator.)
69