Omron SmartSlice GRT1 Series Operation Manual page 136

Slice i/o units
Hide thumbs Also See for SmartSlice GRT1 Series:
Table of Contents

Advertisement

Analog Output Units
Setting Using the
DeviceNet Configurator
1,2,3...
Output range
0 to 5 V (Factory set-
ting)
1 to 5 V
0 to 10 V
–10 to 10 V
Note
1. Always set pin 4 to ON if the DIP switch is used to set the range. If this pin
is OFF, the DIP switch settings will not be enabled.
2. The DIP switch settings are read when the power is turned ON.
GRT1-DA2C
Each pin is set according to the following table.
Pin No.
1
2
3
4
Output range
4 to 20 mA
0 to 20 mA
Use the following procedure to set the output range for each output using the
Configurator.
1. In the Network Configuration Window of the Slice I/O Terminal, double-
click the icon of the Slice I/O Terminal that is to be set. Alternatively, right-
click the icon and select Parameters - Edit. The Edit Device Parameters
Window will be displayed.
2. Click the I/O Module Tab.
3. Click the Edit Button in the I/O Module Tab Page. The Edit Unit Parame-
ters Window will be displayed.
4. Select the tab page for the output where the range is to be changed.
Pin 1
OFF
ON
OFF
ON
Setting
Set output range for Outputs 0, 1. Default setting: All pins OFF
Reserved
Range setting method
Pin 1
OFF
ON
Section 5-5
Pin 2
OFF
Fixed at OFF.
OFF
ON
ON
Specifications
Fixed at OFF.
OFF: Set using Setting Tool.
ON: Set using DIP switch.
Default setting: OFF
Pin 2
Fixed at OFF.
Pin 3
Pin 3
117