Connection Diagram For Lme72.000 - Siemens LME7 Series Basic Documentation

Burner control
Hide thumbs Also See for LME7 Series:
Table of Contents

Advertisement

Note:
The connection diagram shown is merely an example which must be verified in the individual case
depending on the application!
Building Technologies Division
Infrastructure & Cities Sector
13.4 Connection diagram for LME72.000... without
actuator SQM4...
PME72.521...
X2-09
Figure 30: Connection diagram for LME73.000... without actuator SQM4...
When using the LME72.000... without actuator according to application Gas direct
ignition (G), 1-stage or gas direct ignition 1 (G), 1-stage, with valve proving, wire
link Dbr4 must be fitted to the actuator's X2-09 as shown above
Parameter P515.01 must be set to 0
Basic Documentation LME7...
13 PME72.521...
1-stage
Without actuator
With/without valve proving
79/245
CC1P7105en
29.11.2011