Time Table And Settings For Program Sequence Pme71.901 - Siemens LME7 Series Basic Documentation

Burner control
Hide thumbs Also See for LME7 Series:
Table of Contents

Advertisement

12.3 Time table and settings for program sequence PME71.901...

Type
TSA
PME71.901...
tw
max.
Requirement
2.5
3
Factory setting
---
t3n+0.45
Max.
2.5
14
Min.
---
---
Step size
---
---
Function parameter
Air pressure switch input
0 = inactive
1 = active
Repetition in the event of loss of flame at the end of safety time
<2: None
= 2: 1 x
= 3: 2 x
= 4: 3 x
Repetition in the event of loss of flame during operation
<2: None
= 2: 1 x
Valve proving
0: inactive
1: active
Valve proving
0: During prepurge time
1: During postpurge time
Valve proving
0: According to P241.01
1: During prepurge time and postpurge time
Legend
tw
Waiting time
TSA
Safety time
t1
Prepurge time
t3
Preignition time
t3n
Postignition time (P257 +0.3 seconds)
t4
Interval: End safety time - load controller release
t8
Postpurge time
1)
Response time to a change of signal by the air pressure switch (opens) and response time in the event of loss of flame
2)
Response time to a change of signal by the inputs (e.g. pressure switch-min)
3)
Flame detection time
4)
Minimum time td1 + td2 + td3 + td4 if: Parameter P241.00 = 1 (ON, after mains ON, with lockout, P234 (postpurge time) = 0 (postpurging) or P241.01 = 0
5)
Minimum time td1 + td2 + td3 + td4 if: Parameter P241.00 = 1 (ON) and P234 (postpurge time) >0 (postpurging) and P241.01 = 1
Building Technologies Division
Infrastructure & Cities Sector
t1
t3
t3n
P225
P226
P257
P230
4)
min.
ca.
min.
min.
20
3
2.5
19.404+2.1
3.087
2.205+0.3
15.582
1237+2.1
37.485
13.23+0.3
74.97
0+2.1
1.029
0+0.3
3.234
4.851
0.147
0.147
0.294
Parameter number
Basic Documentation LME7...
12 PME71.901...
Times in seconds
t8
t4
t10
P234
t11
P224
5)
ca.
ca.
min.
15
4
15
60
4.851
13.818
58.212
1237
13.818
---
0
0
---
4.851
0.294
---
Factory setting
P235
0
P240.00
0
P240.01
0
P241.00
0
P241.01
1
P241.02
0
t10
Specified time air pressure switch state message (timeout)
t11
Opening time of actuator (timeout)
t12
Closing time of actuator (timeout)
td1
Test atmospheric pressure
td2
Test gas pressure
td3
Test space filling
td4
Test space evacuating
td1
t12
1)
2)
3)
td2
ca.
min.
60
---
---
---
10
58.212
---
---
---
10.29
---
1
0.45
0.45
37.485
---
0.3
0.3
---
1.029
---
---
---
---
0.147
td3
td4
max.
3
2.646
2.646
0
0.147
68/245
CC1P7105en