Analog inputs X1, X2
LG-Ni 1000 W at 0 °C
Pt 1000 W at 0 °C
Analog voltages
(for measured variables
in °C, % or without unit)
Remote setpoints X2
Digital input D1
Analog outputs Y1, Y2

Internal diagram

Connection diagram

Siemens
Building Technologies
Controller measuring range
Max. cable length for dia. 0.6 mm
Controller measuring range
Max. cable length for dia. 0.6 mm
Range
Max. cable length for dia. 0.6 mm
Range
Max. cable length for dia. 0.6 mm
Polling voltage for control commands (D...M)
Current consumption
Range
Maximum current
G
D1 M
X1 M
RWD62
G0
Y1 M
D1
Digital input
G, G0
AC 24 V supply
(
SELV AC 24 V power supply)
M
Ground (G0) for signal inputs, universal inputs and analog outputs
X1
Signal input (main input: LS Ni 1000, Pt 1000 and 0...10 V DC)
Signal input (aux. input: LS Ni 1000, Pt 1000, 0 ...10 V DC and 0...1000 W or
X2
0...10 V DC remote setpoint)
Y1, Y2
Analog outputs
Tool
Communication port for PC (9-pin plug)
RWD62 Universal controller
-50...+150 °C
max. 300 m
-20...+180 °C
max. 300 m
DC 0...10 V corresponding to adjustable
range from –100 to 8000 (°C, °F, % or
no unit)
max. 300 m
0...1000 W corresponding to adjustable
range from –100 to 8000 (°C, °F, % or
no unit)
max. 300 m
DC 15 V
< 15 mA
DC 0...10 V
± 1 m A
X2 M
Tool
Y2
M
9/10