Time Table And Settings For Program Sequence Pme73.831 - Siemens LME7 Series Basic Documentation

Burner control
Hide thumbs Also See for LME7 Series:
Table of Contents

Advertisement

18.5 Time table and settings for program sequence PME73.831...

Type
t1
TSA
P225 4)
PME73.831...
tw
max.
min.
Requirement
2.5
3
30
Factory setting
---
t3n+0.45
29.106+2.1
Max.
2.5
14
1237+2.1
Min.
---
---
0+2.1
Step size
---
---
4.851
Type
Time in seconds
PME73.831...
P259.01
P259.02
approx.
approx.
Requirement
15
15
Factory setting
14.994
14.994
Max.
37.485
37.485
Min.
0
0
Step size
0.147
0.147
Function parameter
Repetition in the event of loss of flame during operation
<2: None
= 2: 1 x
Valve proving
0: Inactive
1: Active
Valve proving
0: During prepurge time
1: During postpurge time
Valve proving
0: According to P241.01
1: During prepurge time and postpurge time
Response time flame error or air pressure switch error
0: 1 second
1: 3 seconds
Intermittent operation after 24 hours of continuous operation
0: OFF
1: ON
Actuator position during prepurge time and postpurge time
0: Purging in low-fire
1: Purging in high-fire
Building Technologies Division
Infrastructure & Cities Sector
t3
t3n
t4
t5
P234
P226
P257
P230
P232
min.
approx.
min.
min.
min.
2
2.5
3
8.5
2.058
2.205+0.3
3.234
8.82
37.485
13.23+0.3
74.97
74.97
1237
1.029
0+0.3
3.234
2.058
0.147
0.147
0.294
0.294
4.851
Parameter number
P240
P241.00
P241.01
P241.02
P254
P239
P515
Basic Documentation LME7...
18 PME73.831...
Time in seconds
t8
t9
t10
t11
t12
P231
P224
P259
P260
5)
approx.
approx.
approx.
approx.
0
3
12
65
65
0
2.94
12.054
67.914
67.914
74.97
13.818
1237
1237
0
0
0
0
0
0.294
0.294
4.851
4.851
Factory setting
0
1
0
0
0
1
1
td1
P254
t22
td2
1)
2)
3)
min.
t9+P254(1/3)
---
---
---
10
---
1
---
---
10.29
---
3
0.45
0.45
37.485
---
1
0.3
---
1.029
---
---
---
---
0.147
td3
td4
max.
3
2.646
2.646
0
0.147
141/245
CC1P7105en
29.11.2011

Hide quick links: