19.2.3 Gas pilot ignition 1 (Gp1/2), 1-stage, with valve proving

Program
SV
Figure 78: Connection diagram fuel train gas pilot ignition 1 (Gp1/2), 1-stage, with valve proving

19.2.4 Gas direct ignition 1 (Gp1/2), 1-stage, with valve proving

Program
SV
Figure 79: Connection diagram fuel train gas direct ignition 1 (Gp1/2), 1-stage, with valve proving
Note:
When valve proving is activated (e.g. on shutdown), the load on the valve's
terminals (according to chapter Technical data/Terminal rating Outputs) is
restricted.
Fuel valve 1 X7-04 pin 4/fuel valve 2 X7-02 pin 3/auxiliary output AUX
Rated voltage
Rated current
Power factor
If the terminal load (according to chapter Technical data/Terminal rating
Outputs) is not reduced (max. rated current 2 A, cos >0.4), the design
lifetime will be reached after about 100,000 burner startup cycles!
Basic Documentation LME7...
19 PME73.840...
Gas pilot 1, 1-stage
Gp1/2
V1
Gp1/2
AC 120 V
50/60 Hz
1 A
cos >0.4
V2
PV
Gas direct 1, 1-stage
V1
V2
AC 230 V
50/60 Hz
1 A
cos >0.4
151/245