Siemens LME7 Series Basic Documentation page 147

Burner control
Hide thumbs Also See for LME7 Series:
Table of Contents

Advertisement

Parameter
Parameter
number
700
Error history
701
Current error:
00: Error code
01: Startup meter reading
02: MMI phase
03: Power value
702
Error history former 1:
00: Error code
01: Startup meter reading
02: MMI phase
03: Power value
711
Error history former 10:
00: Error code
01: Startup meter reading
02: MMI phase
03: Power value
900
Process data
936
Normalized speed
951
Mains voltage
954
Flame intensity
Building Technologies Division
Infrastructure & Cities Sector
Edit
Value range
Read only
2
255
0
999999
---
---
0%
100%
Read only
2
255
0
999999
---
---
0%
100%
Read only
2
255
0
999999
---
---
0%
100%
Read only
0%
100%
Read only
0 V
LME73.000A1:
175 V
LME73.000A2:
350 V
Read only
0%
100%
Basic Documentation LME7...
18 PME73.831...
Resolution
Factory setting
Password level
reading from
level
---
Service
1
1
---
1
---
Service
1
1
---
1
---
Service
1
1
---
1
0,01%
---
Service
1 V
---
Service
1%
---
Service
Password level
writing from level
---
---
---
---
---
---
147/245
CC1P7105en
29.11.2011

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents