Siemens LME7 Series Basic Documentation page 146

Burner control
Hide thumbs Also See for LME7 Series:
Table of Contents

Advertisement

Parameter
Parameter
number
259.00
Opening time of actuator (timeout)
259.01
Opening time of actuator from ignition load to low-fire position
259.02
Opening time of actuator from low-fire to ignition load position
260
Closing time of actuator (timeout)
Actuator position during prepurge time and postpurge time
515
0: Purging in low-fire
1: Purging in high-fire
560
Pneumatic combustion control
0 = off/3-step modulation
1 = PWM fan/analog modulation
2 = air damper/analog modulation
(feedback potentiometer ASZxx.3x required)
600
Power setting
654
Analog input (feedback potentiometer ASZxx.3x required)
0 = 3-position step input
1 = 0...10 V
2 = 0...135 
3 = 0...20 mA
4 = 4...20 mA with lockout at I <4 mA
5 = 4...20 mA
Building Technologies Division
Infrastructure & Cities Sector
Edit
Value range
Edit
0 s
1237 s
Edit
0 s
37.485 s
Edit
0 s
37.485 s
Edit
0 s
1237 s
Edit
0
1
Edit
0
2
Edit
0
5
Basic Documentation LME7...
18 PME73.831...
Resolution
Factory setting
Password level
reading from
level
4.851 s
67.914 s
SO
0.147 s
14.994 s
SO
0.147 s
14.994 s
SO
4.851 s
67.914 s
SO
1
1
SO
1
0
SO
1
0
SO
Password level
writing from level
OEM
OEM
OEM
OEM
OEM
SO
SO
146/245
CC1P7105en
29.11.2011