Parameter number 516 blinks. Press
517 blinks
Now, for the following parameters, proceed as described above:
- P1 low-fire position 517
- P2 high-fire position 518
For parameter number 519, press
By pressing
or
see chapter Setting parameters without index, without direct display. Set the
required maximum speed for the connected fan (also see the supplier's Data
Sheet)
Press
to transfer the setting value to onboard memory
/reset
ESC
By pressing
and return to the selection level for the parameters
Parameter number 519 blinks. Press
644 blinks
Press
for >1 second
/reset
By pressing
or
feeds back to the control can be set (see supplier's Data Sheet)
Press
to transfer the setting value to the onboard memory
/reset
ESC
By pressing
and return to the selection level for the parameters
Parameter number 644 blinks. Press
P0 blinks
By pressing
(display changes to 0A and speed appears blinking) and pressing
A
or
the speed can be changed within the predefined limits (P0max, P0min)
in step sizes of 10 rpm
Press
to transfer the setting value to the onboard memory and the next
/reset
parameter P1
By pressing
(display changes to 1A and speed appears blinking) and pressing
A
or
the speed can be changed within the predefined limits (P1max, P1min)
in step sizes of 10 rpm
Press
to transfer the setting value to the onboard memory and the next
/reset
parameter P2
By pressing
(display changes to 2A and speed appears blinking) and pressing
A
or
the speed can be changed within the predefined limits (P2max, P2min)
in step sizes of 10 rpm
Press
to transfer the setting value to the onboard memory and to complete
/reset
the initial settings
Display shows -END-
Basic Documentation LME7...
27 PWM settings
to select the next parameter. Parameter
for >1 second
/reset
the speed can be changed in step sizes of 10 rpm. Also
(press
and
simultaneously) you leave the entry level
to select the next parameter. Parameter
the number of pulses per revolution (Hall signals) the unit
(press
and
simultaneously) you leave the entry level
to select the next parameter. Parameter
226/245
CC1P7105en
29.11.2011

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents