Cable Lengths; Actuators; Cross-Sectional Areas - Siemens LME7 Series Basic Documentation

Burner control
Hide thumbs Also See for LME7 Series:
Table of Contents

Advertisement

Building Technologies Division
Infrastructure & Cities Sector

4.4 Cable lengths

Mains supply line
Display, BCI
Load controller X5-03
Safety Loop
Safety valve
Fuel valve
Ignition transformer
Remote reset (lay separate cable)
Other lines
Specification as per EN 60730-1
Type of shutdown or interruption of each circuit
Shutdown with microswitch
Mode of operation

4.5 Actuators

CLOSE/ignition position/OPEN
X2-09 pin 1, X2-09 pin 2, X2-09 pin 3
Rated voltage
Rated current
Power factor
Output K2/2 X2-09/7
Rated current
Power factor
Feedback via input of cam V2, depending on the switching contact used in actuator
X2-09/8!

4.6 Cross-sectional areas

The cross-sectional areas of the mains power lines (L, N, and PE) and, if required, the
safety loop (safety limit thermostat, water shortage, etc.) must be sized for rated
currents according to the selected external primary fuse.
The cross-sectional areas of the other cables must be sized in accordance with the
internal unit fuse (max. 6.3 AT).
Min. cross-sectional area
Cable insulation must be suited for the respective temperature and environmental
conditions!
Basic Documentation LME7...
4 Technical data
Max. 100 m (100 pF/m)
For use under the burner hood or in a
control panel
Max. 1 m (100 pF/m)
Max. 30 m (100 pF/m)
Max. 30 m (100 pF/m)
Max. 30 m (100 pF/m)
Max. 30 m (100 pF/m)
Max. 30 m (100 pF/m)
Max. 30 m (100 pF/m)
Max. 30 m (100 pF/m)
1 pole
Type 2 B
1 mio. switching
1 mio. switching
cycles
cycles
AC 120 V 50/60 Hz
AC 230 V 50/60 Hz
0,1 A
0,1 A
Cos >0.6
Cos >0.6
AC 230 V, 50/60 Hz
Max. 1 A
Cos >0.4
0.75 mm²
(single- or multicore to VDE 0100)
32/245
CC1P7105en
29.11.2011