Setting Safety Parameters 675.00/675.01 And Checking The Safety Settings Under Worst-Case Conditions; Procedure; Follow These Steps; Checking Prepurging - Siemens LME7 Series Basic Documentation

Burner control
Hide thumbs Also See for LME7 Series:
Table of Contents

Advertisement

Procedure

Follow these steps

Checking prepurging

Building Technologies Division
Infrastructure & Cities Sector
27.4.4 Setting safety parameters 675.00/675.01 and checking
the safety settings under worst-case conditions
Select test mode (parameter 559) and check the prepurge speed under worst-case
conditions close to the undervoltage limit, or check the ignition load speeds under
worst-case conditions close to the overvoltage limit:
Note:
In test mode (parameter 559, setting value = 2), the normalized PWM signal
(parameter 675.00) for the prepurge phase or the PWM signal (parameter 675.01) for
the ignition phase is output as a fixed value. Start the burner and check the speed, the
volumetric air flow or air pressure under these worst-case conditions by taking
appropriate measures while ensuring compliance with the relevant standards (e.g. EN
676).
Select programming mode for the OEM
Press
and
A
F
Enter the OEM's password via
password
Display changes from PArA to 400: SEt
Press
to select the next parameter group (P500...P600). Display shows
500: PArA
Press
to go to the respective group
/reset
Press
or
to select parameter 559
Press
/reset
Press
or
to set the value (2 test modes)
Press
to transfer the setting value to the onboard memory
/reset
ESC
By pressing
parameter setting level and return to the parameter group
To check the prepurge speed, set the required worst-case conditions close to the
undervoltage limit
Start the burner and check the speed, the volumetric air flow or air pressure by
taking appropriate measures while ensuring compliance with the relevant
standards (e.g. EN 676) in the prepurge phase (P30)
If the worst-case requirements are not satisfied, change safety parameter 675.00
accordingly
Basic Documentation LME7...