Siemens LME7 Series Basic Documentation page 61

Burner control
Hide thumbs Also See for LME7 Series:
Table of Contents

Advertisement

Parameter
Parameter
number
200
Burner control
224
Specified time air pressure switch
225
Prepurge time -2,1 seconds
226
Preignition time
230
Interval: End of safety time – fuel valve 1 ON
231
Interval: Fuel valve 1 ON – pilot valve OFF
234
Postpurge time
240
Repetition in the event of loss of flame during
operation
0 = none
1 = none
2 = 1 x repetition
247
Continuous pilot (during operation)
0 = OFF
1 = ON
257
Postignition time -0.3 seconds
Building Technologies Division
Infrastructure & Cities Sector
Edit
Value range
Min.
Max.
Edit
0 s
13.818 s
Edit
0 s
1237 s
Edit
1.029 s
37.485 s
Edit
3.234 s
74.97 s
Edit
0 s
74.97 s
Edit
0 s
1237 s
Edit
0
2
Edit
0
1
Edit
0 s
13.23 s
Basic Documentation LME7...
11 PME71.402...
Resolution
Factory setting
Password level
reading from level
0.294 s
13.818 s
SO
4.851 s
29.106 s
SO
0.147 s
3.087 s
SO
0.294 s
3.234 s
SO
0.294 s
2.646 s
SO
4.851 s
19.404 s
SO
1
0
SO
1
0
SO
0.147 s
2.205 s
SO
Password level
writing from level
OEM
OEM
OEM
OEM
OEM
OEM
OEM
OEM
OEM
61/245
CC1P7105en
29.11.2011

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents