Building Technologies
4.4 Cable lengths
Mains supply line
Display, BCI
Load controller X5-03
Safety Loop
Safety valve
Fuel valve
Ignition transformer
Remote reset (lay separate cable)
Other lines
Specification as per EN 60730-1
Type of shutdown or interruption of each circuit
Shutdown with microswitch
Mode of operation
4.5 Actuators
CLOSE / ignition position / OPEN
terminal X2-09 pin 1, X2-09 pin 2, X2-
09 pin 3
∂
Rated voltage
∂
Rated current
∂
Power factor
Output K2/2 X2-09 pin 7
∂
Nominal current
∂
Power factor
Feedback via input X2-09 pin 8 on the LME depending on the current load of the
actuator switching contact used (e.g. cam V2)!
4.6 Cross-sectional areas
The cross-sectional areas of the mains power lines (L, N and PE) and, if required, the
safety loop (safety limit thermostat, water shortage, etc.) must be sized for rated
currents according to the selected external primary fuse.
The cross-sectional areas of the other cables must be sized in accordance with the
internal unit fuse (max. 6.3 AT).
Min. cross-sectional area
Cable insulation must be suited for the respective temperature and environmental
conditions!
Basic Documentation LME7...
4 Technical data
Max. 100 m (100 pF/m)
For use under the burner hood or in a
control panel
Max. 1 m (100 pF/m), unshielded
Max. 30 m (100 pF/m), unshielded
Max. 30 m (100 pF/m), unshielded
Max. 30 m (100 pF/m), unshielded
Max. 30 m (100 pF/m), unshielded
Max. 30 m (100 pF/m), unshielded
Max. 30 m (100 pF/m), unshielded
Max. 30 m (100 pF/m), unshielded
1 pole
Type 2 B
1 mio. switching
1 mio. switching
cycles
cycles
AC 120 V 50/60 Hz
AC 230 V 50/60 Hz
0.1 A
0.1 A
Cosι "0.6
Cosι "0.6
AC 120 V 50/60 Hz
AC 230 V 50/60 Hz
Max. 1 A
Max. 1 A
Cosι >0.4
Cosι >0.4
0.75 mm²
(single- or multicore to VDE 0100)
28/106
CC1P7105enr
17.04.2018