Commissioning (software)
4.16 Deleting data
4.16.5

Restoring the default settings of SIMOTION D410

Overview
SIMOTION D410 is supplied with default parameters such as the transmission rate or
PROFIBUS addresses. You can restore the default settings using the DIL switch. This
deletes the following data:
● Non-volatile SIMOTION data in the SIMOTION device
● The backup copy of non-volatile SIMOTION data on the CompactFlash Card
● User data in the "volatile SIMOTION data" area and on the CompactFlash Card
● The communication configuration (IP and DP parameters) on the CompactFlash Card is
All licenses on the CompactFlash Card are retained.
Restoring the default settings using the DIL switch
1. The power supply is shut down.
2. Select the MRES operating mode by
3. Restart the power supply.
4. Change to the required mode by setting the DIL switch.
Note
The default communications parameters are now restored. You must re-configure the
communication parameters of SIMOTION D410.
154
(PMEMORY.XML/PMEMORY.BAK)
set to the factory settings.
– Setting mode selector switches S1 to S3 to OFF AND
– Using the service selector switches to ensure that no service functions are selected
(S4 to S7 = OFF).
(See figure below.)
Figure 4-42
MRES switch position
The SIMOTION user data is deleted. The default settings are loaded. SIMOTION D410
remains in STOP mode.
SIMOTION D410
Commissioning Manual, 02/2012