Setting Sinamics Integrated To The Factory Settings; Restoring The Default Settings For The Simotion D410-2 - Siemens SIMOTION D410-2DP/PN Installation Manual

Table of Contents

Advertisement

Procedure
1. Open the project you want to edit in SIMOTION SCOUT.
2. Go online with the SIMOTION D410-2.
3. Select SIMOTION D410-2 in the Project Navigator and then select the "Delete user data
on card" option from the "Target system" menu.
4. Confirm the "Delete user data on card" prompt with "OK".
The user data is deleted. SINAMICS Integrated goes into offline mode.
7.16.4

Setting SINAMICS Integrated to the factory settings

Requirement
You must be online to SINAMICS Integrated in order to restore its default settings.
Procedure
1. Right-click "SINAMICS_Integrated" in the Project Navigator.
2. Select the "Target device > Restore default settings" command from the shortcut menu.
This restores the delivery state of SINAMICS Integrated.
7.16.5

Restoring the default settings for the SIMOTION D410-2

Overview
SIMOTION D410-2 is supplied with default parameters such as the transmission rate or
PROFIBUS addresses. You can restore the factory settings with the mode selector switch.
The following data is deleted:
● Non-volatile SIMOTION data in the SIMOTION device
● The backup copy of non-volatile SIMOTION data on the CompactFlash card
(PMEMORY.XML/PMEMORY.BAK)
● User data in the "volatile SIMOTION data" area and on the CompactFlash card
● The communication configuration (IP and DP parameters) on the CompactFlash card is set
to the factory settings.
All licenses on the CompactFlash card are retained.
SIMOTION D410-2
Commissioning and Hardware Installation Manual, 01/2015
Commissioning (software)
7.16 Deleting data
237