Main circuit terminal specifications

2.2 Main circuit terminal specifications

2.2.1

Specification of main circuit terminal

Terminal
Terminal
Symbol
Name
R/L1,
AC power
S/L2,
input
T/L3
U, V, W
Inverter output Connect a three-phase squirrel-cage motor.
Power supply
R1/L11,
for control
S1/L21
circuit
Brake unit
P/+, N/-
connection
DC reactor
P/+, P1
connection
PR, PX
Please do not remove or use terminals PR and PX or the jumper connected.
Earth (ground)
2.2.2
Terminal arrangement of the main circuit terminal, power supply and the motor
wiring
400V class
FR-F740-00023 to 00126-EC
R/L1 S/L2 T/L3
Jumper
R1/L11 S1/L21
IM
Power
Motor
supply
14
Connect to the commercial power supply.
Keep these terminals open when using the high power factor
converter (FR-HC, MT-HC) or power regeneration common converter
(FR-CV).
Connected to the AC power supply terminals R/L1 and S/L2. To
retain the fault display and fault output or when using the high power
factor converter (FR-HC, MT-HC) or power regeneration common
converter (FR-CV), remove the jumpers from terminals R/L1 and R1/
L11, and S/L2 and S1/L21 and apply external power to these
terminals.
The power capacity necessary when separate power is supplied from
R1/L11 and S1/L21 differs according to the inverter capacity.
00380 or less : 60VA, 00470 or more : 80VA
Connect the brake unit (FR-BU2, FR-BU, BU and MT-BU5), power
regeneration common converter (FR-CV), high power factor converter
(FR-HC and MT-HC) or power regeneration converter (MT-RC).
For the 01160 or less, remove the jumper across terminals P/+ and
P1 and connect the DC reactor. (Be sure to connect the DC reactor
supplied with the 01800 or more.)
When a DC reactor is not connected, the jumper across terminals P/
+ and P1 should not be removed.
For earthing (grounding) the inverter chassis. Must be earthed
(grounded).
FR-F740-00170, 00250-EC
Jumper
PR
N/-
P/+
PX
Charge lamp
Description
Charge lamp
Jumper
R1/L11 S1/L21
R/L1 S/L2 T/L3
Power supply
Refer
to
page
14
14
20
31
38
-
18
N/-
P/+ PR
Jumper
PX
IM
Motor