Mitsubishi F700 Series Instruction Manual page 34

Hide thumbs Also See for F700 Series:
Table of Contents

Advertisement

Terminal
Terminal
Symbol
Name
10E
Frequency
setting power
supply
10
Frequency
2
setting
(voltage)
Frequency
4
setting
(current)
Frequency
1
setting
auxiliary
Frequency
5
setting
common
PTC
10
thermistor
2
input
*1
Set Pr. 73, Pr. 267, and a voltage/current input switch correctly, then input an analog signal in accordance with the setting.
Applying a voltage signal with voltage/current input switch ON (current input is selected) or a current signal with switch OFF (voltage input is
selected) could cause component damage of the inverter or analog circuit of signal output devices. (For details, refer to page 166.)
Description
When connecting the frequency setting potentiometer at an initial
status, connect it to terminal 10.
Change the input specifications of terminal 2 when connecting it
to terminal 10E. (Refer to page 170 for Pr. 73 Analog input selection.)
Inputting 0 to 5VDC (or 0 to 10V, 0 to 20mA) provides the
maximum output frequency at 5V (10V, 20mA) and makes input
and output proportional. Use Pr. 73 to switch from among input 0
to 5VDC (initial setting), 0 to 10VDC, and 0 to 20mA.
Set the voltage/current input switch in the ON position to select
current input (0 to 20mA).
*1
Inputting 4 to 20mADC (or 0 to 5V, 0 to 10V) provides the
maximum output frequency at 20mA (5V, 10V) makes input and
output proportional. This input signal is valid only when the AU
signal is ON (terminal 2 input is invalid). Use Pr. 267 to switch
from among input 4 to 20mA (initial setting), 0 to 5VDC, and 0 to
10VDC. Set the voltage/current input switch in the OFF position
to select voltage input (0 to 5V/0 to 10V).
Inputting 0 to ±5 VDC or 0 to ±10VDC adds this signal to terminal
2 or 4 frequency setting signal. Use Pr.73 to switch between the
input 0 to ±5VDC and 0 to ±10VDC (initial setting).
Common terminal for frequency setting signal (terminal 2, 1 or 4)
and analog output terminal AM and CA. Do not earth.
For connecting PTC thermistor output.
When PTC thermistor protection is valid (Pr. 561  "9999"), terminal 2
is not available for frequency setting.
Control circuit specifications
Specifications
10VDC±0.4V
Permissible load
current 10mA
5.2VDC±0.2V
Permissible load
current 10mA
Voltage input:
Input resistance
10k± 1k
Maximum
permissible
voltage 20VDC
Current input:
Input resistance
245± 5
Maximum
permissible
current 30mA
*1
Switch 1
Switch 2
Input resistance
10k± 1k
Maximum
permissible voltage
± 20VDC
Adaptive PTC
thermistor
specification
Heat detection
resistance :
500 to 30k
(Set by Pr. 561)
Rated
Refer to
166
166
166
Voltage/current
input switch
4
2
166
166
---- ------- ------ ---
166
100
23
2