Main circuit terminal specifications

2.2 Main circuit terminal specifications

2.2.1

Specification of main circuit terminal

Terminal
Terminal
Symbol
Name
R/L1,
AC power
S/L2,
input
T/L3
U, V, W
Inverter output Connect a three-phase squirrel-cage motor.
Power supply
R1/L11,
for control
S1/L21
circuit
Brake unit
P/+, N/-
connection
DC reactor
P/+, P1
connection
PR, PX
Please do not remove or use terminals PR and PX or the jumper connected.
Earth (ground)
2.2.2
Terminal arrangement of the main circuit terminal, power supply and the motor
wiring
200V class
FR-F720-00046, 00077-NA
R/L1 S/L2 T/L3
Jumper
R1/L11 S1/L21
N/-
Power supply
16
Connect to the commercial power supply.
Keep these terminals open when using the high power factor
converter (FR-HC, MT-HC) or power regeneration common converter
(FR-CV).
Connected to the AC power supply terminals R/L1 and S/L2. To
retain the fault display and fault output or when using the high power
factor converter (FR-HC, MT-HC) or power regeneration common
converter (FR-CV), remove the jumpers from terminals R/L1 and R1/
L11, and S/L2 and S1/L21 and apply external power to these
terminals.
The power capacity necessary when separate power is supplied from
R1/L11 and S1/L21 differs according to the inverter capacity.
200V
FR-F720-00630 or lower
class
400V
FR-F740-00310 or lower
class
Connect the brake unit (FR-BU2, FR-BU, BU and MT-BU5), power
regeneration common converter (FR-CV), high power factor converter
(FR-HC and MT-HC) or power regeneration converter (MT-RC).
For the FR-F720-02330 (FR-F740-01160) or lower, remove the
jumper across terminals P/+ and P1 and connect the DC reactor. (Be
sure to connect the DC reactor supplied with the FR-F720-03160
(FR-F740-01800) or higher.)
When a DC reactor is not connected, the jumper across terminals
P/+ and P1 should not be removed.
For earthing (grounding) the inverter chassis. Must be earthed
(grounded).
Jumper
PR
P/+
PX
IM
Motor
Charge lamp
As this is an inside cover fixing screw,
do not remove it.
Description
FR-F720-00770
60VA
80VA
FR-F740-00380
60VA
60VA
FR-F720-00105 to 00250-NA
R/L1 S/L2 T/L3
Jumper
R1/L11 S1/L21
Power
supply
FR-F720-00930 or higher
80VA
FR-F740-00470 or higher
80VA
Jumper
PR
N/-
P/+
PX
Charge lamp
IM
Motor
Refer
to
page
16
16
25
36
44
-
23