Mitsubishi F700 Series Instruction Manual page 272

Hide thumbs Also See for F700 Series:
Table of Contents

Advertisement

 Output signals
Terminal
Signal
Used
FUP
FDN
RL
PID
Depending on
SLEEP
Pr. 190 to Pr.
196
Y48
Y49
Y50
Y51
Y52
Y53
Y54
SE
SE
*1
When 100 or larger value is set to any of Pr. 190 to Pr. 196 (output terminal function selection), the terminal output has negative logic. (Refer to
page 123 for details)
CAUTION
 Changing the terminal function using any of Pr. 178 to Pr. 189, 190 to Pr. 196 may affect the other functions. Please set
parameters after confirming the function of each terminal.
Function
Output to indicate that the measured
Upper limit output
value signal exceeded the upper limit
value (Pr. 131).
Output when the measured value signal
Lower limit output
falls below the lower limit (Pr. 132).
"Hi" is output to indicate that the output
Forward (reverse)
indication of the parameter unit is forward
rotation direction
rotation (FWD), and "Low" to indicate that
output
it is reverse rotation (REV) or stop (STOP).
During PID
Turns ON during PID control.
control activated
PID output
Turns
ON
interruption
interruption function is performed.
Output when the absolute value of
PID deviation limit
deviation exceeds the limit value.
During pre-
charge operation
Output during the pre-charge operation
During second
pre-charge
operation
Pre-charge time
over
Output when the pre-charged time
exceeds the time set in Pr.764 or Pr.769.
Second pre-
charge time over
Pre-charge level
over
Output when the pre-charged amount
exceeds the set level in Pr.763 or Pr.768.
Second pre-
charge level over
Common terminal for terminals assigned
Output terminal
to FUP signal, FDN signal, RL signal, PID
common
signal, SLEEP signal, and Y48 signal
Description
Pr. 128 =20, 21, 40, 41, 60, 61,
120, 121, 140, 141
Pr. 131 9999
Set 15 or 115 in any of Pr. 190 to Pr.
196.
Pr. 128 =20, 21, 40, 41, 60, 61,
120, 121, 140, 141
Pr. 132 9999
Set 14 or 114 in any of Pr. 190 to Pr.
196.
Set 16 or 116 in any of Pr. 190 to Pr.
196.
Set 47 or 147 in any of Pr. 190 to Pr.
196.
Pr. 575 9999
when
the
PID
output
Set 70 or 170 in any of Pr. 190 to Pr.
196.
Pr. 553 9999
Set 48 or 148 in any of Pr. 190 to Pr.
196.
Set 49 or 149 in any of Pr. 190 to Pr.
196.
Set 50 or 150 in any of Pr. 190 to Pr.
196.
Set 51 or 151 in any of Pr. 190 to Pr.
196.
Set 52 or 152 in any of Pr. 190 to Pr.
196.
Set 53 or 153 in any of Pr. 190 to Pr.
196.
Set 54 or 154 in any of Pr. 190 to Pr.
196.
PID control
Parameter Setting
*1
*1
*1
*1
*1
*1
*1
*1
*1
*1
*1
*1