Mitsubishi F700 Series Instruction Manual page 137

Hide thumbs Also See for F700 Series:
Table of Contents

Advertisement

Function assignment of external
terminal and control
(2) Inverter operation ready signal (RY signal) and inverter running signal (RUN, RUN3 signal)
Power
ON
supply
ON
STF
RH
Pr. 13
Starting
frequency
Reset
processing
ON
RY
RUN
ON
RUN3
Inverter
Start
Start
Status
Signal is
Signal is
OFF
(during
(during
Output
stop)
stop)
Signal
RY
ON
RUN
OFF
OFF
RUN3
OFF
*1
This signal turns OFF during power failure or undervoltage.
*2
Output is shutoff in conditions like a fault and when the MRS signal is ON.
REMARKS
 RUN signal is assigned to the terminal RUN in the initial setting.
(3) Fault output signal (ALM, ALM2 signal)
Inverter fault occurrence
(trip)
Fault output signal(ALM)
Fault output 2 signal(ALM2)
Reset signal(RES)
REMARKS
Refer to page 330 for the inverter fault description.
126
OFF
OFF
ON
DC injection brake
operation point
DC injection
brake
operation
Time
OFF
ON
OFF
OFF
Start
Signal is
Under DC
ON
ON
Injection
(during
Brake
running)
ON
ON
ON
ON
OFF
ON
ON
ON
ON OFF
OFF
ON
ON OFF
Reset processing
(about 1s)
Reset ON
 When the inverter is ready to operate, the output of the operation
ready signal (RY) is ON. It is also ON during inverter running.
 When the output frequency of the inverter rises to or above
Pr. 13 Starting frequency, the output of the inverter running
signal (RUN) is turned ON. During an inverter stop or DC
injection brake operation, the output is OFF.
 The output of the RUN3 signal is ON when the inverter
running and start signals are ON.
(For the RUN3 signal, output is ON if the starting command is
ON even when a fault occurs or the MRS signal is ON.
When using the RY, RUN and RUN3 signals, assign functions to
Pr. 190 to Pr. 196 (output terminal selection function) referring to the
table below.
Pr. 190 to Pr. 196 Setting
Output
Signal
Positive logic
RY
11
RUN
0
RUN3
45
Output Shut Off
*2
Start signal
Start signal
is ON
is OFF
OFF
OFF
ON
OFF
 If the inverter comes to trip, the ALM and ALM2
signals are output.
 The ALM2 signal remains ON during a reset
period after fault occurrence.
 When using the ALM2 signal, set "94 (positive
Time
logic)" or "194 (negative logic)" to any of Pr. 190 to
Pr. 196 (output terminal function selection) to assign
the function to the output terminal.
 The ALM signal is assigned to the A1B1C1
contact in the initial setting.
Negative logic
111
100
145
Automatic Restart after
Instantaneous Power Failure
Coasting
Restarting
Start signal
Start signal
is ON
is OFF
ON
*1
OFF
ON
OFF
ON
ON
ON