Motor Performance Fine Tuning; Motor Performance Fine Tuning; V/F Motor Control Method Tuning; Open Loop Vector (Olv) Motor Control Method Tuning - YASKAWA V1000 Series Technical Manual

Compact vector control drive
Hide thumbs Also See for V1000 Series:
Table of Contents

Advertisement

6.2 Motor Performance Fine Tuning

6.2

Motor Performance Fine Tuning

This section offers helpful information for counteracting oscillation, hunting, or other faults that occur while performing a trial run. Refer to the section
below that corresponds to the motor control method used.
Note: This section describes parameters that are commonly edited. Consult Yaskawa for more information on detailed settings and fine-tuning the drive.

V/f Motor Control Method Tuning

u
Problem
• Motor hunting and oscillation at speeds
between 10 and 40 Hz
• Motor noise
• Motor hunting and oscillation at speeds
up to 40 Hz
• Poor torque or speed response
• Motor hunting and oscillation
• Poor motor torque at speeds below 10 Hz
• Motor hunting and oscillation
• Poor motor torque at low speeds
• Poor motor instability at motor start
• Poor speed precision
<1> Default settings change when the Control Method is changed (A1-02) or a different V/f pattern is selected using parameter E1-03. The default setting shown is for V/f Control.
Note: Use slip compensation to improve speed precision in V/f Control. First make sure that the proper values have been set for the motor rated current to E2-01, motor rated slip
(E2-02), and motor no-load current (E2-03). Next, adjust the slip compensation gain set to C3-01 so that it is between 0.5 to 1.5.
u

Open Loop Vector (OLV) Motor Control Method Tuning

Problem
• Poor motor torque and speed response
• Control motor hunting and oscillation at
speeds between 10 and 40 Hz.
• Poor motor torque and speed response
• Control motor hunting and oscillation at
speeds between 10 and 40 Hz.
• Overvoltage trips when accelerating,
decelerating, or during sudden speed or load
changes.
• Poor motor torque and speed response
• Motor hunting and oscillation.
• Overvoltage trips when accelerating,
decelerating, or during sudden speed or load
changes
• Poor speed response and stability
• Poor speed precision
• Motor noise
• Control motor hunting and oscillation occur
at speeds below 10 Hz.
224
Table 6.1 Parameters for Tuning the Drive in V/f Motor Control Method
Parameter No.
• If insufficient motor torque relative to the size of the load causes hunting,
reduce the setting.
Hunting Prevention Gain
(n1-02)
• When motor hunting and oscillation occur with a light load, increase the
setting.
• If the motor noise is too loud, increase the carrier frequency.
• When motor hunting and oscillation occur at speeds up to 40 Hz, lower the
Carrier Frequency Selection
carrier frequency.
(C6-02)
• The default setting for the carrier frequency depends on the drive capacity (
o2-04) and the Drive Duty Selection (C6-01).
• If motor torque and speed response are too slow, decrease the setting.
Torque Compensation
Primary Delay Time (C4-02)
• If motor hunting and oscillation occur, increase the setting.
• If motor torque is insufficient at speeds below 10 Hz, increase the setting.
Torque Compensation Gain
• If motor hunting and oscillation with a relatively light load, decrease the
(C4-01)
setting.
• If torque is insufficient at speeds below 10 Hz, increase the setting.
Mid Output Voltage A
(E1-08)
• If motor instability occurs at motor start, decrease the setting.
Minimum Output Voltage
Note: The recommended setting value is for 200 V class drives. Double this
(E1-10)
value when using a 400 V class drive.
Slip Compensation Gain
• After setting the motor-rated torque (E2-01), motor-rated slip (E2-02) and
(C3-01)
motor no-load current (E2-03), adjust the slip compensation gain (C3-01).
Table 6.2 Parameters for Tuning the Drive in OLV Motor Control Method
Parameter No.
• If motor torque and speed response are too slow, gradually
decrease the setting by 0.05.
AFR Gain
(n2-01)
• If motor hunting and oscillation occur, gradually increase the
setting by 0.05.
• To improve motor torque speed response, gradually reduce this
setting by 10 ms and check the performance.
• If motor hunting and oscillation occur as a result of load inertia,
AFR Time Constant 1
gradually increase the setting by 50 ms and check the performance.
(n2-02)
Note: Ensure that n2-02 ≤ n2-03. When making adjustments to n2-02,
set C4-02 (Torque Compensation Primary Delay Time Constant 1)
accordingly.
• If overvoltage trips occur, gradually increase this setting by 50 ms.
• If response is slow, gradually reduce this setting by 10 ms.
AFR Time Constant 2
Note: Ensure that n2-02 ≤ n2-03. When making adjustments to n2-03,
(n2-03)
increase the value of C4-06 (Torque Compensation Primary Delay
Time 2) proportionally.
• To improve motor torque speed response, gradually reduce this
setting by 2 ms and check the performance.
Torque Compensation Primary
• If motor hunting and oscillation occur, gradually increase this
Delay Time Constant 1
setting by 10 ms.
(C4-02)
Note: Ensure that C4-02 ≤ C4-06. When making adjustments to
C4-02, increase n2-02 (AFR Time Constant) proportionally.
• If overvoltage trips occur, gradually increase this setting by 10 ms
and check the performance.
• If response is slow, gradually reduce this setting by 2 ms and check
Torque Compensation Primary
the performance.
Delay Time Constant 2 (C4-06)
Note: Ensure that C4-02 ≤ C4-06. When changing C4-06 (Torque
Compensation Primary Delay Time Constant 2), increase the value
of n2-03 proportionally.
• If response is slow, gradually decrease the setting by 10 ms.
Slip Compensation Primary
Delay Time Constant (C3-02)
• If speed is unstable, gradually increase the setting by 10 ms.
• If speed is too slow, gradually increase the setting by 0.1 ms.
Slip Compensation Gain
(C3-01)
• If speed is too fast, gradually decrease the setting by 0.1 ms.
• If there is too much motor noise, the carrier frequency is too high.
• If motor hunting and oscillation occur at low speeds, reduce the
Carrier Frequency Selection
carrier frequency.
(C6-02)
• The default setting for the carrier frequency depends on the drive
capacity (o2-04) and Drive Duty Selection (C6-01).
Countermeasure
Countermeasure
YASKAWA ELECTRIC SIEP C710606 18A YASKAWA AC Drive – V1000 Technical Manual (Preliminary)
Default
Suggested Setting
Value
1.00
0.50 to 2.00
7 (Swing PWM
1 to A
1)
200 ms
100 to 1000 ms
<1>
1.00
0.50 to 1.50
E1-08: 16.0
VE1-10: 12.0
Initial value ±5 V
V
-
0.5 to 1.5
Default Value
Suggested Setting
1.00
0.50 to 2.00
50 ms
50 to 2000 ms
750 ms
750 to 2000 ms
20 ms
20 to 100 ms
<1>
150 ms
150 to 750 ms
200 ms
100 to 500 ms
<1>
1.0
0.5 to 1.5
<1>
7 (Swing PWM 1)
0 to the default setting

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents