4.6

Basic Drive Setup Adjustments

This section explains the basic settings required for initial drive operation. Checking these basic parameter settings during start-up will help to ensure a
successful drive start-up.
If more information is required for parameters not listed in this section,
parameters.
u

Control Mode Selection: A1-02

Available Control Modes
n
Three motor control modes are available. Select the control mode that best suits the application in which the drive will be used.
Control Mode
V/f Control
Open Loop Vector Control
PM Open Loop Vector Control

Initialize Parameter Values: A1-03

u
Parameter A1-03 (Initialize Parameters) resets all parameters to the original default values.
Note: Save all changed parameter settings by setting o2-03="1" before initializing the drive. Your settings will be lost if a 2-wire or 3-wire initialization using 2220, or 3330 if
performed without first saving user parameters.
Different Methods of Drive initialization
n
1110: Resets all parameters to user-defined default values
A user-initialization resets all parameters to a user-defined set of default values previously saved to the drive. Set parameter o2-03 to "2" to clear those
values.
Note: Set o2-03 to "1" to save the current parameter settings and changes for a "user-initialization." After saving all parameter setting changes, parameter o2-03 automatically returns
to 0.
Refer to Verifying Parameter Settings and Backing Up Changes on page
2220: 2-Wire Initialization
Returns all parameters to factory default values for 2-wire control.
3330: 3-Wire Initialization
Returns all parameters to factory default values for 3-wire control.
5550: Uploads Parameter Data from the Removable Control Circuit Terminal Board
Replacing either the removable control circuit terminal board or the drive and applying main power may result in an oPE04 fault. If parameter setting
data in the removable control circuit terminal board is correct, set A1-03 to "5550" to upload the data to the drive.
Note:
Refer to Run Command Input Selection: b1-02 on page 77
Note: Initializing the drive for 2-wire sequence (A1-03 = 2220) returns all drive parameters to factory settings. Back up all parameters in the event of accidental initialization. the
data with 2-wire sequence returns all the set parameters to the factory settings.
u

Application Presets: A1-06

The drive features application presets to facilitate the set up of commonly used applications such as a water supply pump, conveyor, exhaust fan, HVAC
fan, compressor, hoist, and crane. Selecting one of these presets automatically sets the required parameters to the optimum values and changes the
appropriate I/O terminal settings for that specific application.
Verify all I/O signals and external sequences before operating the motor.
application.
Users are able to make further adjustments to these settings using the Setup Mode.
No.
Parameter Name
A1-06
Application Presets
<1> All general-purpose parameters are accessible when A1-06 = 0.

DWEZ Function Selection: A1-07

u
DriveWorksEZ is an independent software package that can be used to operate and monitor the drive with a 2 ms scan. It is fully compatible with all types
of serial communication software available on the market.
YASKAWA ELECTRIC SIEP C710606 18A YASKAWA AC Drive – V1000 Technical Manual (Preliminary)
Refer to Parameter List on page 293
Parameter
• General variable speed applications, particularly useful for running multiple motors from a single drive
A1-02 = 0 (default)
• When replacing a drive in which parameter settings are unknown.
• General variable speed applications
A1-02 = 2
• Applications requiring high precision, high speed control.
A1-02 = 5
Variable torque applications employing permanent magnet motors and energy savings.
Refer to Backing Up Parameter Values: o2-03 on page 96
96.
for more information on a 2-wire and 3-wire sequence.
Refer to Backing Up Parameter Values: o2-03 on page 96
Refer to Application Presets on page 70
Refer to Hoist Application Preset Specifics on page 73
0: General-purpose (A2 parameters are not affected)
1: Water supply pump
2: Conveyor
3: Exhaust fan
4: HVAC fan
5: Air compressor
6: Hoist
7: Crane (hoist, traverse)

4.6 Basic Drive Setup Adjustments

as required for a complete listing of drive
Main Applications
Setting Range
4
when selecting a hoist
Default
0
<1>
75