4.7 Test Run
Jog Operation Procedures
n
Set H1-07 (Multi-Function Contact Input Terminal S7 Function Selection) to "12" (FJOG command).
1.
Turn the power on to the drive. The initial display appears.
2.
Press the
key until the Parameter Setting menu appears.
3.
Press
to enter the Parameter Setting menu.
4.
Press
and
until H1-07 appears. Note: Select a parameter between H1-01 and H1-07.
5.
Press
and set the value for H1-07.
6.
Press
and
until "12" appears on the screen.
Note: At jog operation in reverse run, set multi-function contact input to 13.
7.
Press
to save the setting.
To begin rotating the motor:
Turn the power on to the drive. The initial display appears.
1.
Note: Set the drive to REMOTE.
With multi-function contact input terminal S7 closed, the motor rotates forwards at 6 Hz.
2.
Note: No run command is necessary when using the Jog frequency.
3.
The drive will stop with terminal S7 open.
u

Multi-Step Speed Operation (4-Step Speed)

Select up to 17 preset references (including Jog reference) using five multi-function inputs S3 through S7. Four multi-step references can be selected using
two multi-function inputs as illustrated in
Multi-Step Speed Operation Parameters
n
No.
Name
d1-01
Frequency Reference 1
d1-02
Frequency Reference 2
d1-03
Frequency Reference 3
d1-04
Frequency Reference 4
Digital Input
n
Terminal
S5
S6
Wiring Example
n
Set up external switches SW1 and SW2.
98
Step
Step
Figure 4.32
.
Frequency reference. o1-03 determines the units, with Hz as the default.
Frequency reference when multi-function input "Multi-Step Speed Reference 1" (H1-oo = 3) is on. Setting unit: set by o1-03.
Frequency reference when multi-function input "Multi-Step Speed Reference 2" (H1-oo = 4) is on. Setting unit: set by o1-03.
Frequency reference when multi-function input "Multi-Step Speed Reference 1, 2" (H1-oo = 3 and 4) are both on. Setting unit: set
by o1-03.
Parameter
Setting
H1-05
H1-06
Three-Phase, 200 Vac
(AC400 V)
SW1
SW2
Figure 4.32 Control Terminals for 4 Multi-Step Speeds
Description
3
Multi-Step Speed Reference 1
4
Multi-Step Speed Reference 2
Drive
U/T1
R/L1
V/T2
S/L2
W/T3
T/L3
S5
S6
SC
YASKAWA ELECTRIC SIEP C710606 18A YASKAWA AC Drive – V1000 Technical Manual (Preliminary)
Display/Result
Display/Result
Motor