Wall Termination-With And Without Damper - Heat & Glo Foundation Series Installation And Operating Manual

Co-linear direct vent gas fireplaces
Table of Contents

Advertisement

I. WALL TERMINATION - WITH AND WITHOUT OPTIONAL DAMPER
Wall Termination Without
Optional Mechanical Damper
FRAMING:
8" = 11-3/4" W X 11-3/4" H
10" = 13-1/4" W X 13-1/4" H
INSULATION PAD MUST BE CUT IN
CENTER TO ACCOMMODATE VENT SIZE.
PLACE FOIL SIDE OUT.
Figure 8I.1
Wall Termination With
Optional Mechanical Damper
OPTIONAL MECHANICAL
DRILL 1/4" HOLES
TO MATCH POWER VENT BASE
INSULATION PAD MUST BE CUT IN
CENTER TO ACCOMMODATE VENT SIZE.
PLACE FOIL SIDE OUT.
ACCESS PANEL NEEDED FOR DAMPER MOTOR SERVICE
Minimum recommended size for ease of access is 11 inches wide x 8 inches deep.
Figure 8I.2
Heat & Glo • FDN-4-ST, FDN-5-ST, FDN-6-ST, FDN-7-ST Installation Manual • 16400-9801 Rev. H • 11/19
DRILL 1/4" HOLES
TO MATCH POWER
VENT BASE
FLUE DAMPER
USE HEAVY DUTY FASTENERS
APPROPRIATE
TO YOUR CONSTRUCTION TO
SECURE POWERVENT
8 - VENTING
USE HEAVY DUTY FASTENERS
APPROPRIATE
TO YOUR CONSTRUCTION TO
SECURE POWERVENT
27