B. Installing Wall Shield Firestops and Hori-
zontal Termination Cap
WARNING
Fire Risk
Exhaust Fumes Risk
Impaired Performance of Appliance
• Ensure vent components are locked
together correctly.
• Pipe may separate if not properly joined.
For Horizontal Runs - Wall shield fi restops are REQUIRED on
both sides of a combustible wall through which the vent passes.
NOTE: Model SLK-01TRD does not need an exterior
wall shield fi restop on an exterior combustible wall.
To install wall shield fi restops for horizontal runs that pass
through either interior or exterior walls:
Cut a 10 in. x 10 in. (254 mm x 254 mm) hole for SL-D-
series pipe. The center of the framing hole is one (1) inch
(25.4 mm) above the center of the horizontal vent pipe.
• Position the wall shield fi restops on both sides of the hole
previously cut and secure the wall shield fi restops with
nails or screws.
• The heat shields of the wall shield fi restops MUST BE
placed towards the top of the hole.
• Continue the vent run through the wall shield fi restops.
(25.4 mm)
Figure 8.2 Hole and Vent Pipe
HEAT SHIELD
WALL SHIELD
FIRESTOP
(INTERIOR)
Figure 8.3 Heat Shield, Interior & Exterior Wall Shield Firestops
10 in.
(254 mm)
1 in.
10 in.
(254 mm)
VENT PIPE
TRIM HEAT
SHIELD IF TOO
LONG, ADD TO
SHIELD IF TOO
SHORT
WALL SHIELD
FIRESTOP
(EXTERIOR)
Heat & Glo • Soho24B • 2137-900 Rev. E • 11/07
WARNING
Fire Risk.
Explosion Risk.
Do NOT pack insulation or other
combustibles between fi restops.
• ALWAYS maintain specifi ed clearances around venting
and fi restop systems.
• Install fi restops as specifi ed.
Failure to keep insulation or other material away from vent
pipe may cause fi re.
Installing the Horizontal Termination Cap
Vent termination must not be recessed in the wall. Siding
may be brought to the edge of the cap base.
Flash and seal as appropriate for siding material at outside
edges of cap.
When installing a horizontal termination cap, follow the cap
location guidelines as prescribed by current ANSI Z223.1
and CAN/CGA-B149 installation codes.
WARNING
Burn Risk
• Local codes may require installation of a
cap shield to prevent anything or anyone
from touching the hot cap.
WARNING
Do NOT connect a pipe section to a termination cap
without using the telescoping flue section found on the
termination cap.
Note: Where required, an exterior wall fl ashing is available.
When penetrating a brick wall, a brick extension kit is
available for framing the brick.