TABLE OF CONTENTS PAGE NO. 1. KEY FEATURES 2. UNIT MODEL IDENTIFICATION 3. UNIT MODELS 4. DUCTED SPLIT SYSTEM DESCRIPTION 5. TECHNICAL SPECIFICATIONS 6. DIMENSIONS & WEIGHTS 7. PHYSICAL DATA 8. REFRIGERATION CYCLES 9. EXTERNAL STATIC PRESSURE VERSUS AIR FLOW DATA 10.
Page 7
(Cont.) Key Features The display panel id indoor unit contains the following function indicators : MANUAL Button * This button is used to operate the unit temporarily in case you misplace the remote control or its batteries are exhausted. * Once you push temporary button, the air conditioner will run in such order : Auto, Forced cool, off and back to Auto AUTO The OPERATION lamp is lit, and the air conditioner will run under AUTO mode.
Page 8
(Cont.) Key Features The electronic printed circuit board in the indoor unit is equipped with smart self diagnostic function which automatically stops the operation of the air conditioner in case of a malfunction. Leds Status and Error Code on the display panel of indoor unit ( all sizes ) refer to malfunction reason for easy fast service and maintenance.
Unit Model Identification Source 8 = Miraco Sourced Product Control Type 1 = Standard Wired Control Power Supply 7 = 220-240V / 1ph / 50Hz 5 = 380-420V / 3ph / 50Hz System Capacity kBtu/hr System Size Climate Type T = High Ambient Static Pressure Type M = Medium Static Pressure Family Type...
Page 10
Unit Models 3.1 Unit Models – Export Heat Pump Indoor Unit Outdoor Unit System Compressor Model Model Model Type Supplier 53QDMT12-718 42QDMT12-718 46302363 38QDMT12-718 46302338 Rotary GMCC / Toshiba 53QDMT18-718 42QDMT18-718 46302331 38QDMT18-718 46302405 Rotary GMCC / Toshiba 53QDMT24-718 42QDMT24-718 46302332 38QDMT24-718 46302406...
* For detailed cooling and heating performance, see next pages * Carrier is committed to continuously improving its products according to national and international standards to ensure the highest quality and reliability standards, and to meet market regulations and requirements.
Page 13
* For detailed cooling and heating performance, see next pages * Carrier is committed to continuously improving its products according to national and international standards to ensure the highest quality and reliability standards, and to meet market regulations and requirements.
Page 14
* For detailed cooling and heating performance, see next pages * Carrier is committed to continuously improving its products according to national and international standards to ensure the highest quality and reliability standards, and to meet market regulations and requirements.
7. Physical Data 38QDMT12-718 Outdoor Unit Model 42QDMT12-718 Indoor Unit Model 1Ph, 220-240V~, 50Hz Power supply Ph-V-Hz 13000 Btu/h Capacity 3.81 1265 Input Cooling Rated current 10.28 Btu/wh 3.01 12700 Btu/h Capacity 3.72 1045 Heating Input Rated current 3.56 PH210M2A-4FTS1 Model Rotary Tropical Type...
Page 18
Physical Data (Cont.) 38QDMT18-718 Outdoor Unit Model 42QDMT18-718 Indoor Unit Model 1Ph, 220-240V~, 50Hz Power supply Ph-V-Hz 20500 Btu/h Capacity 6.01 1985 Input Cooling Rated current 10.33 Btu/wh 3.03 19000 Btu/h Capacity 5.57 1695 Heating Input Rated current 3.28 PH340X3C-4KTS1 Model Rotary Tropical Type...
Page 19
Physical Data (Cont.) 38QDMT24-718 Outdoor Unit Model 42QDMT24-718 Indoor Unit Model 1Ph, 220-240V ~ , 50Hz Power supply Ph-V-Hz 25700 Btu/h Capacity 7.53 2415 Input Cooling 11.2 Rated current 10.64 Btu/wh 3.12 23500 Btu/h Capacity 6.89 2125 Heating Input 10.2 Rated current 3.24 2V40S225BUB...
Page 20
Physical Data (Cont.) 38QDMT30-718 Outdoor Unit Model 42QDMT30-718 Indoor Unit Model 1Ph, 220-240V~, 50Hz Power supply Ph-V-Hz 30000 Btu/h Capacity 8.79 3515 Input Cooling 16.3 Rated current 8.53 Btu/wh 2.50 31000 Btu/h Capacity 9.09 2755 Heating Input 12.3 Rated current 3.30 NHT52VBET Model...
Page 21
Physical Data (Cont.) 38QDMT36-718 Outdoor Unit Model 42QDMT36-718 Indoor Unit Model 1Ph, 220-240V ~ , 50Hz Power supply Ph-V-Hz 37300 Btu/h Capacity 10.92 4240 Input Cooling 21.2 Rated current Btu/wh 2.57 38000 Btu/h Capacity 11.14 3360 Heating Input 17.7 Rated current CR47KQM-PFZ Model Reciprocating Tropical...
Page 22
Physical Data (Cont.) 38QDMT36-518 Outdoor Unit Model 42QDMT36-718 Indoor Unit Model 3Ph, 380-420V~, 50Hz Power supply Ph-V-Hz 37000 Btu/h Capacity 10.83 4105 Input Cooling Rated current 9.01 Btu/wh 2.64 36000 Btu/h Capacity 10.55 2100 Heating Input Rated current 3.30 C-SB303H8A Model Scroll Tropical Type...
Page 23
Physical Data (Cont.) 38QDMT42-718 Outdoor Unit Model 42QDMT42-718 Indoor Unit Model 1Ph, 220-240V~, 50Hz Power supply Ph-V-Hz 40000 Btu/h Capacity 11.72 4555 Input Cooling 22.5 Rated current 8.78 Btu/wh 2.57 37500 Btu/h Capacity 10.98 3200 Heating Input 16.9 Rated current 3.43 CR47KQM-PFZ Model...
Page 24
Physical Data (Cont.) 38QDMT42-518 Outdoor Unit Model 42QDMT42-718 Indoor Unit Model 3Ph, 380-420V~, 50Hz Power supply Ph-V-Hz 43000 Btu/h Capacity 12.60 4424 Input Cooling Rated current 9.72 Btu/wh 2.85 41000 Btu/h Capacity 12.02 3092 Heating Input Rated current 3.89 C-SB303H8A Model Scroll Tropical Type...
Page 25
Physical Data (Cont.) 38QDMT48-518 Outdoor Unit Model 42QDMT48-718 Indoor Unit Model 3Ph, 380-420V~, 50Hz Power supply Ph-V-Hz 44500 Btu/h Capacity 13.04 4200 Input Cooling Rated current 10.60 Btu/wh 3.10 47500 Btu/h Capacity 13.92 3795 Heating Input Rated current 3.67 C-SB303H8A Model Scroll Tropical Type...
Page 26
Physical Data (Cont.) 38QDMT60-518 Outdoor Unit Model 42QDMT60-718 Indoor Unit Model 3Ph, 380-420V~, 50Hz Power supply Ph-V-Hz 52300 Btu/h Capacity 15.33 4725 Input Cooling Rated current 11.07 Btu/wh 3.24 55300 Btu/h Capacity 16.21 4155 Heating Input Rated current 3.90 ZR61KH-TFD-522 Model Scroll Tropical Type...
9. External Static Pressure Versus Air Flow Data 9.1 External Static Pressure versus Air Flow 42QDMT12 in.wg 0.04 0.08 0.12 0.16 Air Flow High Speed Medium Speed Low Speed 42QDMT18 in.wg 0.04 0.08 0.12 0.16 0.20 0.24 Air Flow High Speed Medium Speed Low Speed...
Page 38
External Static Pressure Versus Air Flow Data (Cont.) External Static Pressure versus Actual Wet Air Flow (Cont.) 42QDMT24 in.wg 0.04 0.08 0.12 0.16 0.20 0.24 Air Flow High Speed 1280 1208 1158 1103 1041 Medium Speed 1144 1073 1022 Low Speed 42QDMT30 in.wg 0.04...
Page 39
External Static Pressure Versus Air Flow Data (Cont.) External Static Pressure versus Actual Wet Air Flow (Cont.) 42QDMT36 in.wg 0.04 0.08 0.12 0.16 0.20 0.24 0.28 0.32 Air Flow 1080 1036 1005 High Speed 1831 1756 1703 1654 1605 1551 1497 1442 1388...
Page 40
External Static Pressure Versus Air Flow Data (Cont.) External Static Pressure versus Actual Wet Air Flow (Cont.) 42QDMT48 in.wg 0.04 0.08 0.12 0.16 0.20 0.24 0.28 0.32 0.36 0.40 Air Flow 1370 1333 1300 1255 1223 1187 1151 1115 1079 1043 1007 High Speed...
10. Sound Levels Data 10.1 Sound Level Data of Ducted Indoor Units Discharge Return Duct Duct 42QDMT12 in.wg 0.04 0.08 0.12 0.16 1.4 m Sound Level dB(A) dB(A) dB(A) dB(A) dB(A) High Speed 39.6 39.2 38.8 38.5 38.1 Medium Speed 35.4 35.0 34.6...
Page 42
Sound Levels Data (Cont.) Sound Level Data of Ducted Indoor Units (Cont.) 42QDMT36 in.wg 0.04 0.08 0.12 0.16 0.20 0.24 0.28 0.32 Sound Level dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) High Speed 51.5 51.1 50.7 50.4 50.0 49.6 49.2 48.9...
Page 43
Sound Levels Data (Cont.) 10.2 Sound Level Data of Outdoor Units Outdoor Unit Microphone Note : H= 0.5 × height of outdoor unit Model Noise level dB(A) 38QDMT12-718 38QDMT18-718 38QDMT24-718 38QDMT30-718 38QDMT36-718 38QDMT42-718 38QDMT48-518 38QDMT60-518...
11. Operating Limits - Cooling COOLING Dry Bulb Wet Bulb Difference Temp. C° Temp. C° Indoor temperature Maximum Minimum Outdoor temperature Maximum Minimum MAIN POWER SUPPLY Nominal System Minimum Maximum Power Supply Model Voltage Voltage V/PH/HZ 53QDMT12-718 53QDMT18-718 53QDMT24-718 220-240/1/50 53QDMT30-718 53QDMT36-718 53QDMT42-718...
13. Operating Limits - Heating HEATING Dry Bulb Wet Bulb Difference Temp. C° Temp. C° Indoor temperature Maximum Outdoor temperature Maximum Minimum MAIN POWER SUPPLY Nominal System Minimum Maximum Power Supply Model Voltage Voltage V/PH/HZ 53QDMT12-718 53QDMT18-718 53QDMT24-718 220-240/1/50 53QDMT30-718 53QDMT36-718 53QDMT42-718 53QDMT36-518...
15. Electrical Data Electrical Consumption Split Starting System Cooling Circuit Heating Current System Power Breaker 35 °C 43 °C 46 °C 52 °C (Note 1) Model Supply ***** **** Heat Pump V/Ph/Hz Watt Watt Watt Watt Watt 220-240 1265 1330 1355 1400 1045...
17. Optional Accessories For Installation ( Field Supplied ) 17.1 Branched Supply Air Front Panel Branched supply air front panel can be field supplied and installed where desired by using flexible ducts. Comfortable air conditioning can be achieved without affecting the rooms layout or decor.
Page 100
Optional Accessories For Installation ( Field Supplied ) (Cont.) Branched Supply Air Front Panel (Cont.) Indoor Branched Supply Air Front Panel Unit Shape Details Size...
Page 101
Optional Accessories For Installation ( Field Supplied ) (Cont.) 17.2 Convas Air Passage Indoor Branched Supply Air Front Panel Unit Shape Details Size...
Page 102
Optional Accessories For Installation ( Field Supplied ) (Cont.) 17.3 Front panel for Ducted Indoor unit size 12K Front Panel Item Part Name The panel border welding pieces Panel right board Display box assembly Return air grille Panel left board...
Page 103
Optional Accessories For Installation ( Field Supplied ) (Cont.) 17.4 Front panel for Ducted Indoor unit size 18K Front Panel Item Part Name The panel border welding pieces Panel right board Display box assembly Return air grille Panel left board Sponge Display box mounting plate Screws...
Page 104
Optional Accessories For Installation ( Field Supplied ) (Cont.) 17.5 Front panel for Ducted Indoor unit size 24K Front Panel Item Part Name The panel border welding pieces Panel right board Display box assembly Return air grille Panel left board Sponge Display box mounting plate Screws...
Page 105
Optional Accessories For Installation ( Field Supplied ) (Cont.) 17.6 Front panel for Ducted Indoor units sizes 30K – 36K – 42K – 48K – 60K Front Panel Item Part Name The panel border welding pieces Panel right board Display box assembly Return air grille Panel left board Sponge...
18. Troubleshooting Solving steps for typical malfunction (1) For indoor unit a. Indoor air sensor is abnormal Indoor air sensor is abnormal Whether the resistance of the air sensor is 10K Replace indoor air sensor Replace indoor PCB b. Indoor coil sensor is abnormal Indoor coil sensor is abnormal Whether the resistance of indoor coil sensor is Replace indoor coil sensor...
Page 107
Troubleshooting (Cont.) Solving steps for typical malfunction (Cont.) For indoor unit (Cont.) d. Outdoor unit malfunction Outdoor unit malfunction Whether the outdoor unit is power on Check when the power is on Measure whether the voltage of the Replace outdoor unit board communication line’s red and black end between the indoor and outdoor unit is +5V Check the indoor unit main board CN5 or...
Page 108
Troubleshooting (Cont.) Solving steps for typical malfunction (Cont.) For indoor unit (Cont.) f. Full-water malfunction Full-water malfunction Check whether the water-level switch is Insert the water-level switch well inserted well Check whether the water-level switch is broken Replace the water-level switch Check whether the water pump is normal Replace the water pump Check PCB board or replace the main control...
Page 109
Troubleshooting (Cont.) Solving steps for typical malfunction (Cont.) (2) For outdoor unit a. Phase sequence error Phase sequence error Change the order of two of the wires to power supply. Switch on the unit again. If the problem cannot be solved, the outdoor PCB is defective b.
Page 110
Troubleshooting (Cont.) Solving steps for typical malfunction (Cont.) For outdoor unit (Cont.) d. Protection of pressure or temp. Protection of pressure or temp. Is it k1 or K2 open ? Is temp. protective switch K1 open Is pressure protective switch K2 open Possible reason Possible reason 1.
Page 111
Troubleshooting (Cont.) Solving steps for typical malfunction (Cont.) For outdoor unit (Cont.) f. Open-circuit and short-circuit trouble of T4 Repair connector Is connection to connector of temp. sensor good? Check the resistance of the temp. sensor according to Annex 1 Is it the resistance is normal? Replace the sensor Indoor PCB is defective.
Page 112
Troubleshooting (Cont.) Appendix Sensor Resistance Value Table ( °C – K ) Indoor Air Sensor Indoor Coil Sensor Outdoor Coil Sensor °C K Ohm °C K Ohm °C K Ohm °C K Ohm 115.266 12.6431 2.35774 0.62973 108.146 12.0561 2.27249 0.61148 101.517 11.5000...