Commissioning
2.7 First commissioning, vector control mode in the chassis format
2.7.4

Commissioning with STARTER (example)

The table below describes the steps for commissioning the example with STARTER.
Table 2- 13
Sequence for commissioning with STARTER (example)
What to do?
1.
Automatic
configuration
Note:
When the factory setting is p7826 = 1, the firmware is automatically updated to the status on the memory card when a
configured DRIVE-CLiQ component is first booted. This may take a few minutes and is indicated by the READY-LED on
the corresponding components flashing green/red and the Control Unit flashing orange (0.5 Hz). Once all updates have
been completed, the READY-LED on the Control Unit flashes orange at 2 Hz and the corresponding READY-LED on the
components flashes green/red at 2 Hz. For the firmware to be activated, a POWER ON must be carried out for the
components.
2.
Configure the infeed
2.1
Infeed wizard
3.
Configuring drives
3.1
Control structure
100
How to do it?
Operator action:
-> "Project"--> "Connect to target system"
-> Double-click "Automatic configuration"
-> Follow the instructions provided in the wizard.
STARTER then automatically switches to offline
mode.
The infeed must be configured.
Name of infeed -> Double-click "Configuration" ->
Click "Wizard"
The wizard displays the data determined
automatically from the electronic rating plate.
You can now set the line/DC link identification.
The device supply voltage must be entered; the
rated line frequency is automatically
determined/specified for this by the firmware.
"Line filter available" must be active.
With a booksize infeed, one of up to three line filter
types can be selected in the offered menu when this
option is activated.
With a chassis infeed, only one AIM line filter
suitable for the infeed is automatically added with the
above option.
PROFIBUS telegram type 370 must be installed.
This completes the configuration for the infeed.
The drives must be configured individually.
-> "Drives" -> Drive name -> Double-click
"Configuration" -> Click "Configure DDS"
You can activate the function modules.
You can select the control type.
The DRIVE-CLiQ topology is
determined and the electronic
rating plates are read. The data is
then transferred to STARTER.
The next steps are carried out
offline.
If the network environment or
components in the DC link change,
the line/DC link identification
should be carried out again.
Commissioning Manual, (IH1), 01/2011, 6SL3097-4AF00-0BP1