Commissioning
2.13 Commissioning linear motors (servo)
Note
Without using a suitable protective module (e.g. TM120), for safe electrical separation it is
not permissible to connect Temp-F to a Sensor Module of the SINAMICS drive system.
The drive must always be switched into a no-voltage condition. When handling and
connecting Temp-F, when the drive is switched-on, hazardous voltages can be present at
the terminals on the motor side and at the Temp-F connecting cable.
Note
If a 3RN1013-1BW10 thermistor motor protection device or a suitable protective module is
not used, then for safe electrical separation it is not permissible to connect Temp-S to a PLC
or to a Sensor Module of the SINAMICS drive system.
The drive must always be switched into a no-voltage condition. When handling and
connecting Temp-S, when the drive is switched-on, hazardous voltages can be present at
the terminals on the motor side and at the Temp-S connecting cable.
Temperature evaluation unit with safe electrical separation
Terminal Module 120 is a temperature evaluation unit with DRIVE-CLiQ interface for
installation in a control cabinet. The TM120 has 4 measuring channels with safe electrical
separation to connect KTY or PTC temperature sensors. A TM120 can also be used with
Sensor Modules for encoder evaluation (SMCxx, SMIxx and SMExx) if safe electrical
separation of the temperature sensors is necessary.
Evaluating the temperature sensors
See also: Configuration Manual for Linear Motors 1FN3 or 1FN6.
140
Commissioning Manual, (IH1), 01/2011, 6SL3097-4AF00-0BP1
Commissioning Manual