Diagnostics
3.1 Diagnostics via LEDs
Table 3- 47
Meaning of the OPT LED on the Control Unit
LED
Color
OPT
Green
Red
Orange
196
Status
OFF
Electronics power supply is missing or outside permissible
tolerance range.
Communication Board either defective or not inserted.
Continuous
Communication Board is ready and cyclic communication
light
is taking place.
Flashing light
The Communication Board is ready, but cyclic
0.5 Hz
communications is not running.
Possible causes:
At least one fault is present.
Communication is being established.
Continuous
Cyclic communication via PROFINET has not yet been
light
established. However, non-cyclic communications are
possible. SINAMICS waits for a parameterizing/configuring
telegram
Flashing light
The firmware update into the CBE20 has been completed
0.5 Hz
with an error.
Possible causes:
The CBE20 is defective.
The memory card for the Control Unit is defective.
In this state CBE20 cannot be used.
Flashing light
There is a communications error between the Control Unit
2 Hz
and the CBE20.
Possible causes:
Board was withdrawn after booting.
The board is defective
Flashing light
Firmware is being updated.
0.5 Hz
Description, cause
Commissioning Manual, (IH1), 01/2011, 6SL3097-4AF00-0BP1
Remedy
Correctly insert the
board, if required,
replace.