Siemens SIPROTEC 4 7SD80 Manual page 86

Line differential protection
Table of Contents

Advertisement

Functions
2.4 Backup overcurrent
Addr.
Parameter
2613
67-B1 PICKUP
2614
50-B1 DELAY
2614
67-B1 DELAY
2615
50-B1 Inrush
2615
67-B1 Inrush
2616
50N-B1 PICKUP
2616
67N-B1 PICKUP
2617
50N-B1 DELAY
2617
67N-B1 DELAY
2618
50(N)-B1 Pil/BI
2618
67(N)-B1 Pil/BI
2620
Op.Mode50(N)-B2
2620
Op.Mode67(N)-B2
2621
67(N)-B2 Dir.
2622
67(N)-B2 on FFM
2623
50-B2 PICKUP
2623
67-B2 PICKUP
2624
50-B2 DELAY
2624
67-B2 DELAY
2625
50-B2 Inrush
2625
67-B2 Inrush
2626
50N-B2 PICKUP
2626
67N-B2 PICKUP
2627
50N-B2 DELAY
2627
67N-B2 DELAY
2628
50(N)-B2 Pil/BI
86
C
Setting Options
1A
0.10 .. 25.00 A; ∞
5A
0.50 .. 125.00 A; ∞
0.00 .. 30.00 sec; ∞
0.00 .. 30.00 sec; ∞
NO
YES
NO
YES
1A
0.05 .. 25.00 A; ∞
5A
0.25 .. 125.00 A; ∞
1A
0.05 .. 25.00 A; ∞
5A
0.25 .. 125.00 A; ∞
0.00 .. 30.00 sec; ∞
0.00 .. 30.00 sec; ∞
NO
YES
NO
YES
ON
Only Emer. prot
OFF
ON
Only Emer. prot
OFF
Non-Directional
Forward
Reverse
Non-Directional
BLOCKED
1A
0.10 .. 25.00 A; ∞
5A
0.50 .. 125.00 A; ∞
1A
0.10 .. 25.00 A; ∞
5A
0.50 .. 125.00 A; ∞
0.00 .. 30.00 sec; ∞
0.00 .. 30.00 sec; ∞
NO
YES
NO
YES
1A
0.05 .. 25.00 A; ∞
5A
0.25 .. 125.00 A; ∞
1A
0.05 .. 25.00 A; ∞
5A
0.25 .. 125.00 A; ∞
0.00 .. 30.00 sec; ∞
0.00 .. 30.00 sec; ∞
NO
YES
Default Setting
Comments
2.00 A
67-B1 Pickup threshold
10.00 A
0.30 sec
50-B1 Delay
0.30 sec
67-B1 set time delay
NO
50-B1 Inrush blocking
NO
67-B1 Inrush blocking
0.50 A
50N-B1 Pickup
2.50 A
0.50 A
67N-B1 Pickup threshold
2.50 A
2.00 sec
50N-B1 Delay
2.00 sec
67N-B1 set time delay
YES
Instantaneous trip via Pilot
Prot./BI
NO
Instantaneous trip via Pilot
Prot./BI
Only Emer. prot
Operating Mode 50(N)-B2
Only Emer. prot
Operating Mode 67(N)-B2
Non-Directional
67(N)-B2 Direction
BLOCKED
67(N)-B2 Direct. stage on
Fuse Failure
1.50 A
50-B2 Pickup
7.50 A
1.50 A
67-B2 Pickup threshold
7.50 A
0.50 sec
50-B2 Delay
0.50 sec
67-B2 set time delay
NO
50-B2 Inrush blocking
NO
67-B2 Inrush blocking
0.20 A
50N-B2 Pickup
1.00 A
0.20 A
67N-B2 Pickup threshold
1.00 A
2.00 sec
50N-B2 Delay
2.00 sec
67N-B2 set time delay
NO
Instantaneous trip via Pilot
Prot./BI
SIPROTEC 4, 7SD80, Manual
E50417-G1100-C474-A2, Edition 02.2018