[anschl-3-stromwdl-summenstromw-060606, 1, en_US]
Figure C-3
Important: Grounding of the cable shield must be effected at the cable side
The switchover of the current polarity (address 201) also reverses the polarity of the current input IN!
[anschl-u1e-u2e-u3e-abgang-20070129, 1, en_US]
Figure C-4
SIPROTEC 4, 7SD80, Manual
E50417-G1100-C474-A2, Edition 02.2018
Current transformer connections to three current transformers, ground current from addi-
tional summation current transformer – preferably for effectively or low-resistance grounded
networks
Example for the connection type "VAN, VBN, VCN" with voltage connection on the feeder side
C.1 Connection Examples for Current and Voltage Transformers
Connection Examples
315