Isolated interface for data transfer to a control center
Terminal
Test voltage (PELV)
Transmission speed
Bridgeable distance
Profibus RS485 (DP)
Terminal
Test voltage (PELV)
Transmission speed
Bridgeable distance
Profibus FO (DP)
FO connector type
Terminal
Transmission speed
Recommended:
Optical wavelength
Laser Class 1 according to EN 60825-1/-2
Permissible optical signal attenuation
Bridgeable distance
DNP3.0 /MODBUS RS485
Terminal
Test voltage (PELV)
Transmission speed
Bridgeable distance
DNP3.0 /MODBUS FO
FO connector type
Terminal
Transmission speed
Optical wavelength
Laser Class 1 according to EN 60825-1/-2
Permissible optical signal attenuation
Bridgeable distance
Ethernet electrical (EN 100) for DIGSI, IEC61850
Terminal
SIPROTEC 4, 7SD80, Manual
E50417-G1100-C474-A2, Edition 02.2018
Back case bottom, mounting location "B", RJ45 socket
500 V; 50 Hz
min. 2,400 Bd, max. 57,600 Bd;
factory setting 19,200 Bd
max. 1 km
Back case bottom, mounting location "B", 9- pin DSUB socket
500 V; 50 Hz
Up to 1.5 MBd
1 000 m (3 300 ft) at ≤ 93.75 kBd
500 m (1 600 ft) at ≤ 187.5 kBd
200 m (660 ft) at ≤ 1.5 MBd
ST connector
Double ring
Back case bottom, mounting location "B"
bis 1.5 MBd
> 500 kBd with normal casing
λ = 820 nm
When using glass fiber 50/125 μm or glass fiber 62.5/125 μm
max. 8 dB, with glass fiber 62.5/125 μm
max. 1.5 km
Back case bottom, mounting location "B", 9- pin DSUB socket
500 V; 50 Hz
up to 19,200 Bd
max. 1 km
ST connector transmitter/receiver
Back case bottom, mounting location "B"
up to 19,200 Bd
λ = 820 nm
When using glass fiber 50 μm/125 μm or glass fiber 62.5/125 μm
max. 8 dB, with glass fiber 62.5/125 μm
max. 1.5 km
Back case bottom, mounting location "B",
2 x RJ45 socket
100BaseT according to IEEE802.3
Technical Data