Checking a Connection Using Direct Link
In case of an optical fiber link (as shown in
connection is checked as follows:
•
Both devices at the link ends have to be switched on.
•
Check in the event log or in the spontaneous annunciations:
–
If the message
with the device index of the other device in case of an optical fiber conductor, a link has been estab-
lished and one device has recognized the other.
–
If the message
with the device index of the other device in case of a copper connection, a link has been established
and one device has recognized the other.
–
The device indicates
been detected.
•
In case of an incorrect communication link, the indication
faulty (no. 3232) is displayed. In this case, check the connection again:
–
Are the connections correct and not swapped?
–
Are the cables free from mechanical damage, intact and the connectors locked?
–
Otherwise repeat the verification.
Continue with the margin heading "Consistency of Connection and Parameterization".
Consistency of Connection and Parameterization
Having performed the above checks, the linking of a device pair has been completely tested and connected to
auxiliary supply voltage. Now the devices contact each other on their own account.
SIPROTEC 4, 7SD80, Manual
E50417-G1100-C474-A2, Edition 02.2018
Direct connection of the PC to the device using the CU protection data interface – basic
example
Connection of the PC via modem - basic example
PDI FO con. to. (protection data interface connected with no. 3243) is provided
PDI Cu con. to. (protection data interface connected with no. 3244) is provided
Slave Login , no. 3492 or Master Login , no. 3491 if the other device has
Figure 3-27
or
Figure
3-29) or via copper conductor link, this
PDI FO faulty (no. 3230) or PDI Cu
Mounting and Commissioning
3.3 Commissioning