Siemens SIPROTEC 4 7SD80 Manual page 341

Line differential protection
Table of Contents

Advertisement

Addr. Parameter
2202
Trip Time DELAY
2203
Iph rel.Trip
2204
3I0 rel.Trip
2301
INRUSH REST.
2302
2nd HARMONIC
2303
CROSS BLOCK
2305
MAX INRUSH PEAK InRushRestraint 1A
2310
CROSSB 2HM
2603A 67N dir. meas.
2610
Op.Mode50(N)-B1
2610
Op.Mode67(N)-B1
2611
67(N)-B1 Dir.
2612
67(N)-B1 on FFM
2613
50-B1 PICKUP
2613
67-B1 PICKUP
2614
50-B1 DELAY
2614
67-B1 DELAY
2615
50-B1 Inrush
2615
67-B1 Inrush
2616
50N-B1 PICKUP
2616
67N-B1 PICKUP
2617
50N-B1 DELAY
2617
67N-B1 DELAY
2618
50(N)-B1 Pil/BI
SIPROTEC 4, 7SD80, Manual
E50417-G1100-C474-A2, Edition 02.2018
Function
C
Setting Options
DTT Direct Trip
0.00 .. 30.00 sec; ∞ 0.00 sec
DTT Direct Trip
1A
0.0 .. 25.0 A; ∞
5A
0.0 .. 125.0 A; ∞
DTT Direct Trip
1A
0.0 .. 25.0 A; ∞
5A
0.0 .. 125.0 A; ∞
InRushRestraint
OFF
ON
InRushRestraint
10 .. 45 %
InRushRestraint
NO
YES
1.1 .. 25.0 A
5A
5.5 .. 125.0 A
InRushRestraint
0.00 .. 60.00 sec; ∞ 0.00 sec
Back-Up O/C
V0/I0 or V2/I2
with V0/I0
with V2/I2
Back-Up O/C
ON
Only Emer. prot
OFF
Back-Up O/C
ON
Only Emer. prot
OFF
Back-Up O/C
Non-Directional
Forward
Reverse
Back-Up O/C
Non-Directional
BLOCKED
Back-Up O/C
1A
0.10 .. 25.00 A; ∞
5A
0.50 .. 125.00 A; ∞ 10.00 A
Back-Up O/C
1A
0.10 .. 25.00 A; ∞
5A
0.50 .. 125.00 A; ∞ 10.00 A
Back-Up O/C
0.00 .. 30.00 sec; ∞ 0.30 sec
Back-Up O/C
0.00 .. 30.00 sec; ∞ 0.30 sec
Back-Up O/C
NO
YES
Back-Up O/C
NO
YES
Back-Up O/C
1A
0.05 .. 25.00 A; ∞
5A
0.25 .. 125.00 A; ∞ 2.50 A
Back-Up O/C
1A
0.05 .. 25.00 A; ∞
5A
0.25 .. 125.00 A; ∞ 2.50 A
Back-Up O/C
0.00 .. 30.00 sec; ∞ 2.00 sec
Back-Up O/C
0.00 .. 30.00 sec; ∞ 2.00 sec
Back-Up O/C
NO
YES
Functions, Settings, Information
Default Setting
Comments
Trip Time Delay
0.0 A
Minimal Phase Current to
release trip
0.0 A
0.0 A
Minimal 3I0 Current to
release trip
0.0 A
OFF
Inrush Restraint
15 %
2nd. harmonic in % of
fundamental
NO
Cross Block
15.0 A
Maximum inrush-peak
value
75.0 A
Time for Crossblock with
2nd harmonic
V0/I0 or V2/I2
67N, Measurement of
direction
OFF
Operating Mode 50(N)-B1
OFF
Operating Mode 67(N)-B1
Non-Directional
67(N)-B1 Direction
BLOCKED
67(N)-B1 Direct. stage on
Fuse Failure
2.00 A
50-B1 Pickup
2.00 A
67-B1 Pickup threshold
50-B1 Delay
67-B1 set time delay
NO
50-B1 Inrush blocking
NO
67-B1 Inrush blocking
0.50 A
50N-B1 Pickup
0.50 A
67N-B1 Pickup threshold
50N-B1 Delay
67N-B1 set time delay
YES
Instantaneous trip via
Pilot Prot./BI
F.2 Settings
341