Frequency Protection 81 (Optional)
Monitoring of falling below (f<) and/or exceeding (f>) with 4 frequency limits and time delays that are
independently adjustable
Particularly insensitive to harmonics and abrupt phase angle changesbesonders unempfindlich gegen
Oberschwingungen und Phasensprünge
Wide frequency range (approx. 25 Hz to 70 Hz)
Automatic Reclose Function (Optional)
For reclosing after 3-pole open condition
2 reclosing attempts
With separate action times for each reclosing attempt, optionally without action times
With separate dead times
Optionally controlled by protection element pickup with separate dead times after 1-pole, 2-pole or 3-
pole pickup
Monitoring Functions
Reliability of the device is greatly increased because of self-monitoring of the internal measurement
circuits, the auxiliary power supply as well as the hardware and software
Monitoring of the current transformer and voltage transformer secondary circuits using summation and
symmetry check techniques
Monitoring of communication with statistics showing the availability of transmission telegrams
Check of the consistency of protection settings at both line ends: no processor system start-up with
inconsistent settings which could lead to a malfunction of the differential protection system
Trip circuit monitoring possible
Check of local and remote measured values and comparison of both
Broken wire supervision for the secondary CT circuits with fast phase segregated blocking of the differen-
tial protection system in order to avoid malfunction
Supervision of measuring voltage failure using "Fuse Failure Monitor"
Flexible Protection Functions
Up to 20 customizable protection functions with 3-phase or 1-phase operation
Any calculated or directly measured variable can theoretically be evaluated
Standard protection logic with a constant (i.e. definite time) characteristic curve
Internal and configurable pickup and dropout delay
Editable indication texts
User-defined Logic Functions (CFC)
Internal and external signals can be logically combined to realize user-defined logic functions
All common logic functions
Time delays and limit value interrogations