Siemens SIPROTEC 4 7SD80 Manual page 172

Line differential protection
Table of Contents

Advertisement

Functions
2.15 Flexible Protection Functions
Parameter OPERRAT. MODE = 3-phase
Positive seq.,
Negative seq.,
Zero sequence
Parameter MEAS. QUANTITY = Current
Parameter MEAS. METHOD
Ratio I2/I1
Parameter MEAS. QUANTITY = Voltage
Parameter VOLTAGE
SYSTEM
Phase-Phase
Phase-Ground
NOTE
i
i
We see a special behavior of the phase-selective pickup indications for the 3-phase voltage protection with
phase-to-phase quantities, as the phase-selective pickup indication "Flx01 Pickup Lx" is assigned to the
corresponding measured value channel "Lx".
Table 2-9
Parameter OPERRAT. MODE = 1-phase
Parameter MEAS. QUANTITY = Current or Voltage
Parameter
MEAS. METHOD
Fundamental
True RMS
Parameter MEAS. QUANTITY = Current
Parameter CURRENT
Ia
Ib
Ic
In
In sensitive
Parameter MEAS. QUANTITY = Voltage
Parameter VOLTAGE
172
In order to realize certain applications, the positive sequence system or negative
sequence system can be configured as measurement procedure. Examples are:
- I2 (tripping monitoring system)
- U2 (voltage asymmetry)
Via the selection zero sequence system, additional zero sequence current or zero
sequence voltage functions can be realized that operate independent of the ground varia-
bles IN and VN, which are measured directly via transformers.
Important: The voltage threshold is always parameterized according to the definition of
the balanced components independently of parameter VOLTAGE SYSTEM.
The ratio of the negative-sequence current to the positive-sequence current is evaluated.
Please note that the function only operates ifΙ2 or Ι1 has exceeded the threshold value
0.1 · Ι
.
N
You can select whether a three-phase operating voltage function must evaluate the
phase-to-ground or phase-to-phase voltages.
When selecting phase-to-phase, these variables are derived from the phase-to-ground
voltages. The selection is, for example, important for single-pole faults. If the faulty
voltage drops to zero, the affected phase-to-ground voltage is thus zero, and the respec-
tive phase-to-phase voltages drop to the variable of a phase-to-ground voltage.
Parameter in the Setting Dialog "Measurement Procedure", Mode of Operation 1-phase
Only the fundamental harmonic is evaluated, higher harmonics are suppressed. This is
the standard measurement procedure of the protection functions.
The "True" RMS value is determined, i.e. higher harmonics are evaluated. This procedure
is applied, for example, if an overload protection element must be realized on the basis of
a current measurement, as the higher harmonics contribute to thermal heating.
It is determined which current-measuring channel must be evaluated by the function.
Depending on the device version, either IN (normal-sensitive ground current input) or INS
(sensitive ground current input) is offered.
SIPROTEC 4, 7SD80, Manual
E50417-G1100-C474-A2, Edition 02.2018

Advertisement

Table of Contents
loading

Table of Contents