Siemens SIPROTEC 4 7SD80 Manual page 348

Line differential protection
Table of Contents

Advertisement

Functions, Settings, Information
F.2 Settings
Addr. Parameter
3722
59G-1-3V0PICKUP
3723
59G-1-3V0 DELAY
3724
59G-2-3V0PICKUP
3725
59G-2-3V0 DELAY
3728A 59G-3Vo Stabil.
3729A 59G RESET
3731
59-V1 Mode
3732
59-1-V1 PICKUP
3733
59-1-V1 DELAY
3734
59-2-V1 PICKUP
3735
59-2-V1 DELAY
3739A 59-V1 RESET
3741
59-V2 Mode
3742
59-1-V2 PICKUP
3743
59-1-V2 DELAY
3744
59-2-V2 PICKUP
3745
59-2-V2 DELAY
3749A 59-V2 RESET
3751
27-Vph-g Mode
3752
27-1-Vph PICKUP
3753
27-1-Vph DELAY
3754
27-2-Vph PICKUP
3755
27-2-Vph DELAY
348
Function
C
Setting Options
27/59 O/U Volt.
1.0 .. 220.0 V; ∞
27/59 O/U Volt.
0.00 .. 100.00 sec;
27/59 O/U Volt.
1.0 .. 220.0 V; ∞
27/59 O/U Volt.
0.00 .. 100.00 sec;
27/59 O/U Volt.
ON
OFF
27/59 O/U Volt.
0.30 .. 0.99
27/59 O/U Volt.
OFF
Alarm Only
ON
V>Alarm V>>Trip
27/59 O/U Volt.
2.0 .. 220.0 V; ∞
27/59 O/U Volt.
0.00 .. 100.00 sec;
27/59 O/U Volt.
2.0 .. 220.0 V; ∞
27/59 O/U Volt.
0.00 .. 100.00 sec;
27/59 O/U Volt.
0.30 .. 0.99
27/59 O/U Volt.
OFF
Alarm Only
ON
V>Alarm V>>Trip
27/59 O/U Volt.
2.0 .. 220.0 V; ∞
27/59 O/U Volt.
0.00 .. 100.00 sec;
27/59 O/U Volt.
2.0 .. 220.0 V; ∞
27/59 O/U Volt.
0.00 .. 100.00 sec;
27/59 O/U Volt.
0.30 .. 0.99
27/59 O/U Volt.
OFF
Alarm Only
ON
V<Alarm V<<Trip
27/59 O/U Volt.
1.0 .. 100.0 V; 0
27/59 O/U Volt.
0.00 .. 100.00 sec;
27/59 O/U Volt.
1.0 .. 100.0 V; 0
27/59 O/U Volt.
0.00 .. 100.00 sec;
Default Setting
Comments
30.0 V
59G-1 Pickup 3V0 (zero
seq.)
2.00 sec
59G-1 Time Delay
50.0 V
59G-2 Pickup 3V0 (zero
seq.)
1.00 sec
59G-2 Time Delay
ON
59G: Stabilization 3Vo-
Measurement
0.95
Reset ratio
OFF
Operating mode V1 over-
voltage prot.
150.0 V
59-1 Pickup Overvoltage
(pos. seq.)
2.00 sec
59-1 Time Delay
175.0 V
59-2 Pickup Overvoltage
(pos. seq.)
1.00 sec
59-2 Time Delay
0.98
Reset ratio
OFF
Operating mode V2 over-
voltage prot.
30.0 V
59-1 Pickup Overvoltage
(neg. seq.)
2.00 sec
59-1 Time Delay
50.0 V
59-2 Pickup Overvoltage
(neg. seq.)
1.00 sec
59-2 Time Delay
0.98
Reset ratio
OFF
Operating mode Vph-g
undervoltage prot.
30.0 V
27-1 Pickup Undervoltage
(phase-neutral)
2.00 sec
27-1 Time Delay
10.0 V
27-2 Pickup Undervoltage
(phase-neutral)
1.00 sec
27-2 Time Delay
SIPROTEC 4, 7SD80, Manual
E50417-G1100-C474-A2, Edition 02.2018