EMC Tests for Immunity (Type Tests)
Standards:
1 MHz test, class III IEC 60255-22-1, IEC 61000-4-18, IEEE
C37.90.1
Electrostatic discharge, class IV
IEC 60255-22-2, IEC 61000-4-2
Irradiation with HF field, amplitude-modulated, class III
IEC 60255-22-3, IEC 61000-4-3
Fast transient disturbances/burst, class IV
IEC 60255-22-4, IEC 61000-4-4, IEEE C37.90.1
High-energy surge voltages installation classIII IEC 60255-22-5,
IEC 61000-4-5
Line-conducted high frequency, amplitude-modulated, class III
IEC 60255-22-6, IEC 61000-4-6
Power system frequency magnetic field
IEC 61000-4-8, Klasse IV;
Radiated electromagnetic interference
IEEE Std C37.90.2
Damped oscillations
IEC 61000-4-18
EMC Tests for Noise Emission Test (Type Test)
Standard:
Radio noise voltage to lines, only auxiliary voltage
IEC-CISPR 11
Interference field strength
IEC-CISPR 11
SIPROTEC 4, 7SD80, Manual
E50417-G1100-C474-A2, Edition 02.2018
Auxiliary voltage
Measuring inputs and relay outputs
Binary inputs
CU protection interface, unscreened, a and
b
CU protection interface, screened
IEC 60255-6 and -22, (product standards)
IEC/EN 61000-6-2
VDE 0435
For more standards, see the individual
tests
2.5 kV (Peak); 1 MHz; τ = 15 µs; 400
Surges per s; Test duration 2 s; R
8 kV contact discharge; 15 kV air
discharge; both polarities; 150 pF; R
330 Ω
10 V/m; 80 MHz to 1 GHz; 1.4 GHz to 2.7
GHz 80 % AM; 1 kHz
4 kV; 5 ns/50 ns; 5 kHz; burst length =
15 ms; repetition rate 300 ms; both polari-
ties; R
= 50 Ω; test duration 1 min
i
Impuls: 1.2 µs/50 µs
common mode: 4 kV; 12 Ω; 9 µF
diff. mode: 1 kV; 2 Ω; 18 µF
common mode: 4 kV; 42 Ω; 0.5 µF
diff. mode: 1 kV; 42 Ω; 0.5 µF
common mode: 4 kV; 42 Ω; 0.5 µF
diff. mode: 1 kV; 42 Ω; gas-filled tube
common mode: 4 kV; 42 Ω; gas-filled tube
common mode: 4 kV; 2 Ω;
coupling into shield
10 V; 150 kHz to 80 MHz; 80 % AM; 1 kHz
30 A/m continuous; 300 A/m for 3 s;
20 V/m; 80 MHz to 1 GHz; 80 % AM; 1 kHz
35 V/m; 80 MHz to 1GHz; 100 % pulse 1 Hz
rep. rate 50% duty cycle
2.5 kV (peak); 100 kHz; 40 pulses per s;
test duration 2 s; Ri = 200 Ω
IEC/EN 61000-6-4
150 kHz to 30 MHz Limit Class A
30 MHz to 1000 MHz Limit Class A
Technical Data
4.1 General Device Data