Siemens SIPROTEC 4 7SD80 Manual page 60

Line differential protection
Table of Contents

Advertisement

Functions
2.2 Phase Comparison Protection and Ground Differential Protection
[lo-esd-anr-20101116, 2, en_US]
Figure 2-14
If only the V0 voltage is connected, only parameter 1226 87N L: 3V0> is effective. The threshold checks
87N L:Vph-g min and 87N L:Vph-g max (parameter 1227 and 1228) are not relevant.
You will find the logic diagram for the differential protection trip in Section
Logic and Tripping
60
Ground fault differential protection pickup, isolated/resonant-grounded system
Logic.
2.2.5 Differential Protection Pickup
SIPROTEC 4, 7SD80, Manual
E50417-G1100-C474-A2, Edition 02.2018