2.1.4.1

Functional Description

The data of a fault event can be read out via the device interface and evaluated with the help of the SIGRA 4
graphic analysis software. SIGRA 4 graphically represents the data recorded during the fault event and also
calculates additional information from the measured values. Currents and voltages can be presented either as
primary or as secondary values. Signals are additionally recorded as binary tracks (marks) e.g. "pickup", "trip".
If port B of the device has been configured correspondingly, the fault record data can be imported by a central
controller via this interface and evaluated. Currents and voltages are prepared for a graphic representation.
Signals are additionally recorded as binary tracks (marks) e.g. "pickup", "trip".
The retrieval of the fault data by the central controller takes place automatically either after each protection
pickup or after a tipping.
NOTE
i
i
The signals used for the binary tracks can be allocated in DIGSI.
2.1.4.2

Setting Notes

Specifications
The actual storage time encompasses the pre-fault time PRE. TRIG. TIME (address 411) ahead of the refer-
ence instant, the normal recording time and the post-fault time POST REC. TIME (address 412) after the
storage criterion has reset. The maximum storage time for each fault recording (MAX. LENGTH) is entered in
address 410. Recording per fault must not exceed 5 seconds. A total of 8 records can be saved. However, the
total length of time of all fault records in the buffer must not exceed 25 seconds.
2.1.4.3

Settings

Addresses which have an appended "A" can only be changed with DIGSI, under "Additional Settings".
Addr.
Parameter
402A
WAVEFORMTRIGGER
403A
WAVEFORM DATA
410
MAX. LENGTH
411
PRE. TRIG. TIME
412
POST REC. TIME
415
BinIn CAPT.TIME
2.1.4.4

Information List

No.
Information
-
FltRecSta
4
>Trig.Wave.Cap.
30053
Fault rec. run.

Change Group

2.1.5
Up to four different setting groups can be created for establishing the device's function settings.
40
Setting Options
Save w. Pickup
Save w. TRIP
Start w. TRIP
Fault event
Pow.Sys.Flt.
0.30 .. 5.00 sec
0.05 .. 0.50 sec
0.05 .. 0.50 sec
0.10 .. 5.00 sec
Type of
Comments
Informa-
tion
IntSP
Fault Recording Start
SP
>Trigger Waveform Capture
OUT
Fault recording is running
Default Setting
Comments
Save w. Pickup
Waveform Capture
Fault event
Scope of Waveform Data
2.00 sec
Max. length of a Waveform
Capture Record
0.25 sec
Captured Waveform Prior to
Trigger
0.10 sec
Captured Waveform after Event
0.50 sec
Capture Time via Binary Input
E50417-G1100-C474-A2, Edition 02.2018
SIPROTEC 4, 7SD80, Manual