Introduction
1.3 Characteristics
Command Processing
Switching devices can be opened and closed manually using control keys, programmable function keys,
via port B (e.g. of SICAM or SCADA), or via the user interface (using a personal computer and the DIGSI
operating software)
Feedback of the circuit-breaker states via the breaker auxiliary contacts (for commands with feedback)
Plausibility monitoring of the circuit-breaker positions and interlocking conditions.
Commissioning; Operation; Maintenance
Indication of the local and remote measured values according to magnitude and phase angle
Indication of the calculated differential and restraint currents
Indication of the measured values of the communication connection, as runtime and availability
Additional Functions
Battery-buffered clock which can be synchronized via a synchronization signal (DCF77, IRIGB via satellite
receiver), binary input or system interface
Continuous calculation and indication of operational measured values on the front display, indication of
measured values of the far end or all ends (for devices with active interfaces)
Fault event memory (trip log) for the last eight network faults (faults in the power system), with real time
stamps
Fault recording and data transfer for fault recording for a maximum time range of 15 seconds.
Switching statistics: Counting of the trip and close commands initiated by the device as well as recording
of the short-circuit data and accumulation of the disconnected fault currents
Communication with central control and memory components via serial interfaces possible (depending
on the ordered variant), optionally via RS232, RS485 connection, modem or fiber optic cable
Commissioning aids such as connection check, direction check and circuit-breaker check
28
SIPROTEC 4, 7SD80, Manual
E50417-G1100-C474-A2, Edition 02.2018