System parameter 4: Selecting the dimensions for output via fieldbus (mm / inch).
system parameter:
bus readout value in
*0.001 (LAAS10/..40)
Fig. 64: Selecting the dimensions for the fieldbus output
The multiplication factor of the output is determined by the type of sensors being used.
Sensor types
LAAS10, LAAS10+,
LAAS40 and LAAS40+
LAAS200 and LAAS200+
LAAS10, LAAS10+, LAAS200, LAAS200+ are in preparation
System parameter 5: Setting the display time
system parameter:
display time
2.0 s
Fig. 65: Setting the display time
The maximal measured values (peak values) for the specified time are displayed here(holding
time). This time is for the display only. Values between 0.0 seconds and 2.0 seconds can be set.
System parameter 6: Setting the bus address.
system parameter:
bus address
Fig. 66: Setting the fieldbus address
•
Profibus:
•
DeviceNet:
•
CanOpen:
•
ProfiNet IO:
•
CC-Link:
•
EtherNet/IP: ---
•
EtherCAT:
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Double Sheet Control System R1000 series L20
with integrated fieldbus interface
4
mm
Multiplication factor (at inch resp. mm)
5
6
1
1 - 125
0 - 63
1 - 127
---
1 – 63
---
Manual
0,0001 inch or 0,001mm
0,001 inch or 0,01mm
Start-up