Roland R1000 Series Manual page 64

Double sheet control system with integrated fieldbus interface
Hide thumbs Also See for R1000 Series:
Table of Contents

Advertisement

Communication with the PLC
6.6.6
EDS file for EtherNet/IP
The EDS file contains the specific configuration data of the device. The data must be known to the
controller.
The manufacturers of the controller supply the tools for the integration of the EDS file into the
network. Roland Electronic does not supply such tools, because they have to be compatible with
the interface design of the controller.
The EDS file is supplied on a CD or can be downloaded from the Roland homepage.
By pressing the key "
64
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Double Sheet Control System R1000 series L20
with integrated fieldbus interface
Note
24 Bytes I/O must be set.
" status indicators are shown on the display.
Nr.
LED
LED 1 Link (Activity) LED configuration 1 (Default)
LED 2 Module
Status
LED 3 Network
Status
LED 4 Activity
Status
Manual
Status Indicators
State
Description
Off
Link not sensed
Green
Link sensed
LED configuration 3 (Default)
Off
No power
Green
Controlled by a scanner in Run state
Green, flashing
Not controlled, or scanner in Idle state
Red, flashing
A minor recoverable fault has been detected
Red
A major unrecoverable fault has been detected
Alternating
Self test in progress
Red / Green
LED configuration 3 (Default)
Off
No power or no IP address
Green
On line, one or more connections established
(CIP Class 1 or 3)
Green, flashing
On line, no connections established
Red
Duplicate IP address, fatal error
Red, flashing
One or more connections timed out
(CIP Class 1 or 3)
Alternating
Self-test in progress
Red / Green
Green, flashing
The activity led flashes green each time a packet
is received or transmitted
B0063191 / 1.3