The following tables show the loading sequence for a
30GX350 chiller. Each compressor has 2 loaders and the chill-
ers are configured for staged circuit loading. See Note 2.
COMP
LOADER
STAGE
A1
0
0
1
1
2
1
3
1
4
1
5
1
6
1
7
1
8
1
9
1
CLOSE CONTROL LOADING SEQUENCE (CIRCUIT A LEAD CIRCUIT, 4-COMPRESSOR UNIT)
COMP
LOADER
STAGE
A1
0
0
1
1
2
1
3
1
3A
1
4
1
5
1
6
1
7
1
8
1
8A
1
9
1
10
1
LEGEND
0 — Off
1 — On
NOTES:
1. Stages 3A and 8A are not used by the algorithm when increasing stages.
Stages 3 and 8 are not used by the algorithm when decreasing stages.
2. The loading sequence for 30GX281-325 units is the same as those shown
for the 30GX350 above.
APPENDIX B (cont)
STANDARD LOADING SEQUENCE (CIRCUIT A LEAD CIRCUIT, 4-COMPRESSOR UNIT)
LOADER
COMP
A1
A2
A2
0
0
0
0
0
0
1
0
0
1
1
0
1
0
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
LOADER
COMP
A1
A2
A2
0
0
0
0
0
0
1
0
0
1
1
0
0
0
1
1
0
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
COMP
LOADER
LOADER
B1
B1
0
0
0
0
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
COMP
LOADER
LOADER
B1
B1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
0
1
1
1
1
1
0
1
1
1
1
85
% TOTAL
COMP
CAPACITY
B2
B2
(50/50 Split)
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
0
0
1
1
1
% TOTAL
COMP
CAPACITY
B2
B2
(50/50 Split)
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
0
0
1
0
1
1
1
0.0
10.0
18.0
25.0
35.0
50.0
68.0
75.0
85.0
100.0
0.0
10.0
18.0
25.0
20.0
35.0
50.0
60.0
68.0
75.0
70.0
85.0
100.0