Table 36 — Alarm and Alert Codes (cont)
WHY WAS THIS
DESCRIPTION
ALARM GENERATED?
Circuit A High
After first 90 seconds,
Saturated Suction
SST > 55 F (12.8 C) and
Temperature
EXV < 1% for 5 minutes
Circuit B High
After first 90 seconds,
Saturated Suction
SST > 55 F (12.8 C) and
Temperature
EXV < 1% for 5 minutes
Loss of Condenser
Flow switch not closed
Flow
within 1 minute after
pump is started or if flow
switch opens during nor-
mal operation for
> 10 seconds
Illegal Configuration x
Illegal Configuration has
been entered. Correction
needed.
Initial Configuration
No configuration has
Required
been entered.
Unit is in Emergency
CCN command received
Stop
to shut unit down.
Cooler Pump Interlock
Interlock did not close
Failed at Start-Up
within 1 minute after
transition
Cooler Pump Interlock
Interlock opened for at
Opened Unexpectedly
least 5 seconds during
operation
Cooler Pump Interlock
Interlock closed when
Closed When Pump OFF
pump relay is off
Loss of Communication
No communications have
with WSM
been received by PSIO-1
within 5 minutes of trans-
mission.
Circuit A Liquid Level
Sensor reads 245 F
Sensor Failure
(118 C) or -40 F (-40 C)
with SST > 9 F (-12.8 C)
Circuit B Liquid Level
Sensor reads 245 F
Sensor Failure
(118 C) or -40 F (-40 C)
with SST > 9 F (-12.8 C)
Compressor A1
Oil Pump did not build
Pre-Start Oil Pressure
sufficient pressure during
pre-lube cycle.
Compressor A2
Oil Pump did not build
Pre-Start Oil Pressure
sufficient pressure during
pre-lube cycle.
Compressor B1
Oil Pump did not build
Pre-Start Oil Pressure
sufficient pressure during
pre-lube cycle.
Compressor A2
Oil Pump did not build
Pre-Start Oil Pressure
sufficient pressure during
pre-lube cycle.
Circuit A&B OFF for
Control has shut down
Alerts. Unit down
both circuits due to
alerts.
Circuit A Loss of Charge Discharge pressure
reading < 10 PSIG for
30 seconds
Circuit B Loss of Charge Discharge pressure
reading < 10 PSIG for
30 seconds
Loss of Communication
No communications
with FSM
have been received by
PSIO-1 within 5 minutes
of last transmission.
Circuit A High
SCT > MCT_SP + 5 F
Discharge Pressure
(2.8 C)
Circuit B High
SCT > MCT_SP + 5 F
Discharge Pressure
(2.8 C)
High Leaving Chilled
LCW read > LCW Delta
Water Temperature
Alarm limit and total
capacity is 100% and
current LCW > LCW
reading 1 minute ago
ACTION TAKEN
BY CONTROL
Circuit A shut down
Circuit B shut down
Chiller shut down
Chiller cannot start. See
Table 38.
Chiller cannot start
Chiller shut down
Chiller shut down. Pump
turned off.
Chiller shut down. Pump
turned off.
Cooler pump remains off.
Unit prevented from
starting.
WSM forces removed.
Runs under own
control.
Runs, but controls EXV
based on Disch. Super-
heat
Runs, but controls EXV
based on Disch. Super-
heat
Circuit cannot start
Circuit cannot start
Circuit cannot start
Circuit cannot start
None
Circuit A shut down
Circuit B shut down
FSM forces removed
Runs under own
control
Circuit shut down
Circuit shut down
Alert only. None.
49
PROBABLE
RESET METHOD
CAUSE
Manual
Faulty expansion valve,
liquid level sensor or
transducer.
Manual
Faulty expansion valve,
liquid level sensor or
transducer.
Manual
Low condenser water
flow, failed condenser
pump
Manual
Configuration error.
Manual
Configuration omitted.
CCN/Automatic
Network command
Automatic
Failure of cooler pump,
cooler pump interlock, or
flow switch
Automatic
Failure of cooler pump,
cooler pump interlock, or
flow switch
Manual
Failure of cooler pump
relay or interlock, welded
contacts
Automatic
Failed module, wiring
error, failed transformer,
loose connection plug,
wrong address
Automatic
Thermistor circuit open,
faulty liquid level sensor,
wiring error
Automatic
Thermistor circuit open,
faulty liquid level sensor,
wiring error
Manual
Low oil, oil pump failure,
oil solenoid failure, oil
transducer failure, check
valve failed open, oil shut-
off valve closed
Manual
Low oil, oil pump failure,
oil solenoid failure, oil
transducer failure, check
valve failed open, oil shut-
off valve closed
Manual
Low oil, oil pump failure,
oil solenoid failure, oil
transducer failure, check
valve failed open, oil shut-
off valve closed
Manual
Low oil, oil pump failure,
oil solenoid failure, oil
transducer failure, check
valve failed open, oil shut-
off valve closed
Automatic
Check individual alarms
Manual
Refrigerant leak or
transducer failure
Manual
Automatic
Wiring faulty or module
failure
Automatic**
Faulty transducer/high
pressure switch, low/
restricted condenser air/
water flow††
Automatic**
Faulty transducer/high
pressure switch, low/
restricted condenser air/
water flow††
Automatic
Building load greater
than unit capacity, low
water/brine flow, or com-
pressor fault. Check for
other alarms or alerts.