Carrier AQUASNAP 30RAP010-150 Start Up & Operation Manual

Carrier AQUASNAP 30RAP010-150 Start Up & Operation Manual

Air-cooled chillers with comfortlink controls
Table of Contents

Advertisement

Controls, Start-Up, Operation,
Service, and Troubleshooting
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . 2,3
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
Conventions Used in this Manual. . . . . . . . . . . . . . . . . . . .3
Basic Controls Usage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
CONTROLS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-43
General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Main Base Board (MBB) . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Energy Management Module (EMM) . . . . . . . . . . . . . . . .23
Current Sensor Board (CSB) . . . . . . . . . . . . . . . . . . . . . . .23
AUX Board (AUX) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Expansion Valve Board (EXV) . . . . . . . . . . . . . . . . . . . . . .23
Compressor Expansion Board (CXB) . . . . . . . . . . . . . .23
Enable/Off/Remote Contact Switch . . . . . . . . . . . . . . . . .23
Emergency On/Off Switch . . . . . . . . . . . . . . . . . . . . . . . . . .23
Board Addresses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Control Module Communication . . . . . . . . . . . . . . . . . . . .23
®
Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
Energy Management Module . . . . . . . . . . . . . . . . . . . . . . .26
Loss-of-Cooler Flow Protection. . . . . . . . . . . . . . . . . . . . .26
Electronic Expansion Valves (EXV) . . . . . . . . . . . . . . . . .26
Capacity Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Head Pressure Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
Cooling Set Point Select. . . . . . . . . . . . . . . . . . . . . . . . . . . .32
Cooling Set Point (4 to 20 mA). . . . . . . . . . . . . . . . . . . . . .32
Low Sound Mode Operation . . . . . . . . . . . . . . . . . . . . . . . .32
Heating Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
Service Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
Cooler Pump Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
Cooler Pump Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
Cooler Pump Sequence of Operation . . . . . . . . . . . . . . .33
Temperature Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
Demand Limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41
(4 to 20 mA Controlled)
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53300097-01
CONTENTS
Page
(CCN) Interface . . . . . . . . . .24
Printed in U.S.A.
Air-Cooled Chillers
with ComfortLink Controls
Digital Scroll Option. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
• DIGITAL SCROLL OPERATION
PRE-START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
System Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
START-UP AND OPERATION . . . . . . . . . . . . . . . . . . . . 43-45
Actual Start-Up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Check Refrigerant Charge . . . . . . . . . . . . . . . . . . . . . . . . . 44
Charge Adjustment for Brine Operation . . . . . . . . . . . 44
Operating Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
OPERATION SEQUENCE . . . . . . . . . . . . . . . . . . . . . .45,46
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46-64
Electronic Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
• CONTROL COMPONENTS
Electronic Expansion Valve (EXV) . . . . . . . . . . . . . . . 46
EXV Troubleshooting Procedure . . . . . . . . . . . . . . . . . . . 46
• FIELD SERVICING INSTRUCTIONS
Compressor Replacement . . . . . . . . . . . . . . . . . . . . . . . 50
Cooler. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
REPLACEMENT
• BRAZED-PLATE COOLER HEAT EXCHANGER
CLEANING
Oil Charge. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Check Refrigerant Feed Components . . . . . . . . . . . . . . 51
• FILTER DRIER
• MOISTURE-LIQUID INDICATOR
• MINIMUM LOAD VALVE
• PRESSURE RELIEF DEVICES
Check Unit Safeties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
• HIGH-PRESSURE SWITCH
• PRESSURE TRANSDUCERS
• HEATER CABLE
• WINTER SHUTDOWN
Thermistors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Pressure Transducers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Chilled Water Flow Switch. . . . . . . . . . . . . . . . . . . . . . . . . . 54
Strainer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Condenser Fans. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
V Controller . . . . . . . . . . . . . . . . . . . . . . . . . 59
®
• GENERAL OPERATION
• CONFIGURATION
Form 30RAP-4T
Pg 1
®
AQUASNAP
30RAP010-150
Page
7-12
Replaces: 30RAP-3T

Advertisement

Table of Contents

Troubleshooting

loading

Summary of Contents for Carrier AQUASNAP 30RAP010-150

  • Page 1: Table Of Contents

    SERVICE ........46-64 (CCN) Interface ..24 Carrier Comfort Network ®...
  • Page 2: Safety Considerations

    CONTENTS (cont) WARNING Page • EPM CHIP DO NOT VENT refrigerant relief valves within a building. • LOSS OF CCN COMMUNICATIONS Outlet from relief valves must be vented outdoors in • REPLACING DEFECTIVE MODULES accordance with the latest edition of ANSI/ASHRAE Hydronic Package.
  • Page 3: General

    32 F (0° C). Proof of flow switch and strainer are The CCN (Carrier Comfort Network ® ) point names are also factory installed on all models. Do NOT remove power...
  • Page 4 When a specific item is located, the item name alternates so that the item value flashes. Use the arrow keys to ENTER with the value. Press the key at a changeable item change the value or state and press the key to accept ENTER ENTER...
  • Page 5 Timed override is in effect. This is a 1 to 4 hour temporary override of the programmed schedule, forcing unit to Occupied mode. Override can be implemented with unit under Local (Enable) or CCN (Carrier Comfort Network ® ) control. Override expires after each use.
  • Page 6: Controls

    ACCESSORY NAVIGATOR™ DISPLAY MODULE — Pressing will cause the “OFF” to flash. Use the up ENTER The Navigator module provides a mobile user interface to the or down arrow to change “OFF” to “ON”. Pressing ENTER ComfortLink control system, which is only available as a field- will illuminate all LEDs and display all pixels in the view installed accessory.
  • Page 7 LOCATED OVER EMM AND EXV FB-1 TRAN CSB-A1 DISCONNECT OPTION/TB CWP1 CWP2 CWP1 CWP2 C-A1 COMPRESSOR CONTROL BOX a30-4962 Fig. 3 — Typical Control Box for 30RAP010,015 LOCATED OVER EMM AND EXV FB-1 TRAN CCB-2 CCB-1 FB-3 CSB-A1 CSB-A2 DISCONNECT OPTION/TB CWP1 CWP2...
  • Page 8 a30-4964...
  • Page 9 a30-5453...
  • Page 10 a30-5376 Fig. 7A — Typical Wiring Schematic, 30RAP010,015 Units — Power Wiring...
  • Page 11 a30-5377 Fig. 7B — Typical Wiring Schematic, 30RAP010,015 Units — Control Wiring...
  • Page 12 STANDARD OPTIONAL TERMINAL CH-A1 DISCONNECT BLOCK 380V,460V,575V CB1A TB1A CCB-1 ONLY CSB-A1 COMP A1 GRN/YEL CH-A2 BLU BLK CCB-2 CSB-A2 COMP A2 GRN/YEL EQUIP GND 208/230V ONLY CHILLED WATER PUMP FIOP MS-CWP1 CWP1 CWP1 WATER PUMP TRAN3 GRN/YEL SECONDARY MS-CWP2 CWP2 115V GRN/YEL...
  • Page 13 5 AMPS TRAN1 SEE NOTE 9 MBB J1-2 PL1-3 PL1-4 8 AMPS SECONDARY 24V MP-A1 UPC GND GRN/YEL CWFS 3 SEE NOTE 10 PL1-7 PL1-8 J10A EXV J1-2 MP-A2 LVT J12-5 RLY 11 CWP1 MLV-A MLV ACCSY RLY 9 LEGEND SEE NOTE 7 TERMINAL BLOCK TERMINAL (UNMARKED)
  • Page 14 STANDARD OPTIONAL CH-A1 TERMINAL DISCONNECT BLOCK 380V,460V,575V CCB-1 CB1A ONLY TB1A CSB-A1 COMP A1 GRN/YEL CH-A2 BLU BLK CCB-2 CSB-A2 COMP A2 GRN/YEL EQUIP GND CH-B1 380V,460V,575V CCB-3 ONLY CSB-B1 COMP B1 GRN/YEL TRAN3 CH-B2 BLU BLK SECONDARY 115V CCB-4 GRN/YEL CSB-B2 GFI-CO...
  • Page 15 a30-5378 5 AMPS TRAN1 SEE NOTE 10 MBB J1-2 PL1-3 PL1-4 8 AMPS SECONDARY 24V MP-A1 UPC GND GRN/YEL CWFS 3 SEE NOTE 11 PL1-7 PL1-8 J10A MP-A2 LVT J12-5 SEE NOTE 12 PL2-3 PL2-4 MP-B1 RLY 11 CWP1 SEE NOTE 13 PL2-7 PL2-8 MLV-A...
  • Page 16 a30-5454 Fig. 10A — Typical Wiring Schematic, 30RAP070-090 Units — Power Wiring...
  • Page 17 8 AMPS TRAN1 SEE NOTE 10 MBB J1-2 PL1-3 PL1-4 5 AMPS SECONDARY 24V MP-A1 AUX1 J1-12 GRN/YEL UPC GND PL2-3 PL2-4 J10A 12 AMPS MP-A2 PL4-3 PL4-4 MP-B1 RLY 11 PL5-3 PL5-4 LVT J10-16 MP-B2 PL3-3 PL3-4 MP-A3 080-090 ONLY RLY 9 PL6-3...
  • Page 18 OPTIONAL STANDARD DISCONNECT TERMINAL (SINGLE POINT,380/460/575V ONLY) BLOCK CCB-1 CB1A TB1A CSB-A1 COMP A1 GRN/YEL CCB-2 CSB-A2 COMP A2 GRN/YEL CCB-3 CSB-A3 (115 ONLY) COMP A3 SINGLE POINT GRN/YEL ONLY CCB-4 CSB-B1 EQUIP GND COMP B1 FUSE TRAN REPLACE UNIT VOLTAGE NUMBER WITH SIZE...
  • Page 19 8 AMPS TRAN1 PL1-3 PL1-4 MP-A1 MBB J1-2 5 AMPS SECONDARY 24V AUX1 J1-12 PL2-3 PL2-4 GRN/YEL UPC GND MP-A2 J10A 12 AMPS PL4-3 PL4-4 MP-B1 PL5-3 PL5-4 RLY 11 MP-B2 LVT J10-16 PL3-3 PL3-4 MP-A3 PL6-3 PL6-4 MP-B3 RLY 9 RLY 10 HPS-B J10B...
  • Page 20 OPTIONAL STANDARD DISCONNECT TERMINAL (SINGLE POINT,380V,460V,575V ONLY) BLOCK DISCONNECT OPTION ONLY, CONNECT CCB-1 CB1A TO TERMINAL BLOCK FOR STANDARD TB1A CSB-A1 COMP A1 GRN/YEL CCB-2 CSB-A2 COMP A2 GRN/YEL CCB-3 CSB-A3 COMP A3 SINGLE POINT GRN/YEL CCB-4 ONLY CSB-B1 EQUIP GND COMP B1 FUSE TRAN...
  • Page 21 8 AMPS TRAN1 MBB J1-2 PL1-3 PL1-4 5 AMPS SECONDARY 24V MP-A1 AUX1 J1-12 GRN/YEL UPC GND a30-5456 J10A CB 4 PL2-3 PL2-4 12 AMPS MP-A2 PL4-3 PL4-4 MP-B1 RLY 11 PL5-3 PL5-4 LVT J10-16 MP-B2 PL3-3 PL3-4 MP-A3 RLY 9 PL6-3 PL6-4 MP-B3...
  • Page 22: Main Base Board (Mbb)

    LEN (Local Equipment Network). The CCN channel information received from its inputs and from all other (Carrier Comfort Network) bus is also supported. Connections modules. The MBB receives inputs from the discharge and to both LEN and CCN buses are made at the LVT (low voltage suction pressure transducers and thermistors.
  • Page 23: Energy Management Module (Emm)

    a30-5381 Fig. 14 — CCN Wiring Diagram The EMM Energy Management Module (EMM) — module is available as a factory-installed option or as a field- installed accessory. The EMM module receives 4 to 20 mA inputs for the leaving fluid temperature reset, cooling set point and demand limit functions.
  • Page 24: Carrier Comfort Network

    Cooler / Pump Heater YELLOW LED — The MBB has one yellow LED. The Crankcase Heater Relay Output, Circuit B Carrier Comfort Network (CCN) LED will blink during times Energize Compressor B3 of network communication. Energize Compressor A3 (080,090,115,130,150) ®...
  • Page 25: Sensors

    BUS (PLUG) AT UNIT sensor includes a terminal block (SEN) and a RJ11 female CCN- connector. The RJ11 connector is used access into the Carrier Comfort Network (CCN) at the sensor. ® To connect the space temperature sensor (Fig. 16): 1.
  • Page 26: Energy Management Module

    This A proof-of- Energy Management Module (Fig. 18) — Loss-of-Cooler Flow Protection — factory-installed option (FIOP) or field-installed accessory is cooler flow device is factory installed in all chillers. It is recom- used for the following types of temperature reset, demand mended that proper operation of the switch be verified on a reg- limit, and/or ice features: ular basis.
  • Page 27: Minutes Left For Start

    The standard control has an automatic lead-lag feature built LEAD/LAG DETERMINATION — This is a configurable in which determines the wear factor (combination of starts and choice and is factory set to be automatic for all units. The run hours) for each compressor. If all compressors are off and 30RAP units offer an optional digital compressor.
  • Page 28 Table 8 — Part Load Data Percent Displacement, Standard Units with Minimum Load Valve CAPACITY STEPS CAPACITY % CONTROL 30RAP UNIT SIZE STEPS % Displacement Circuit A Circuit B — — — — — — *Minimum Load Valve energized. NOTE: These capacity steps may vary due to different capacity staging sequences.
  • Page 29: Head Pressure Control

    2 STARTS DEADBAND EXAMPLE 1000 3 STARTS TIME (SECONDS) STANDARD DEADBAND LEGEND MODIFIED DEADBAND LWT — Leaving Water Temperature Fig. 19 — Deadband Multiplier Minimum Load Control — If equipped, the minimum load Fan On Set Point (F.ON) equals Head Set Point (Set ...
  • Page 30: Operation Of Machine Based On Control Method And Cooling Set Point Selection Settings

    a30-5459 OFM1 130-150 100-150 OFM1 ONLY ONLY OFM2 OFM3 OFM5 OFM7 OFM9 OFM1 TOP VIEW TOP VIEW SIZES 010,015 SIZES 018-030 OFM2 OFM4 OFM6 OFM8 OFM10 OFM1 OFM3 OFM1 TOP VIEW NOT ON 080-150 SIZES 070-150 100,130 ONLY OFM3 OFM2 OFM4 OFM2 TOP VIEW...
  • Page 31 Table 9 — Fan Stages FAN STAGES 30RAP UNIT SIZE Fan Stage Contactor Energized Fans Operating 010,015 Stage 1 OFM1 Stage 1 OFM1 018-030 Stage 2 FC1,2 OFM1,2 Stage 1 OFM3 035-050 Stage 2 OFM1,2 Stage 3 FC1,2 OFM1,2,3 Stage 1 OFM4 Stage 2 FC1,3...
  • Page 32: Cooling Set Point Select

    possible. This results in operation at increased saturated con- Cooling Set Point Select densing temperature. As a result, some models may not be able SINGLE — Unit operation is based on Cooling Set Point 1 to achieve rated efficiency. For chiller operation at rated effi- ...
  • Page 33: Optional Factory-Installed Hydronic Package

    The pump(s) in the hydronic package come factory As stated before, there are certain alarm conditions and pre-wired into the main unit power supply/starter. In order to Operating Modes that will turn the cooler pump relay ON. This check proper pump rotation, use the Service Test function to sequence will describe the normal operation of the pump test the condenser fans and observe them for proper rotation.
  • Page 34 factory-installed package, an auxiliary set of contacts is wired Selection, any pump that has an active alert will not be allowed to the MBB to serve as Chilled Water Pump Interlock. When to start. the mechanical cooling is called for, the pump interlock and With the dual integral pump package, the Cooler Pump flow switch is checked.
  • Page 35: Configuring And Operating Dual Chiller Control

    Connections can be chiller the Slave chiller will operate in a Stand-Alone mode. made to the CCN screw terminals on LVT. Refer to Carrier If the Emergency Stop switch is turned off or an alarm is Comfort Network ®...
  • Page 36 Table 11 — Dual Chiller Configuration (Master Chiller Example) SUB-MODE ITEM KEYPAD ENTRY DISPLAY ITEM EXPANSION COMMENTS DISP UNIT OPT1 CTRL CONTROL METHOD ENTER OPT2 CTRL SWITCH DEFAULT 0 ENTER OPT2 ESCAPE CCNA CCN ADDRESS DEFAULT 1 ENTER CCNB CCNB CCN BUS NUMBER DEFAULT 0 ENTER...
  • Page 37 Table 11 — Dual Chiller Configuration (Master Chiller Example) (cont) SUB-MODE ITEM KEYPAD ENTRY DISPLAY ITEM EXPANSION COMMENTS CRST COOLING RESET TYPE ENTER LLEN LEAD/LAG CHILLER ENABLE 15 ITEMS LLEN DSBL SCROLLING STOPS ENTER DSBL VALUE FLASHES ENTER ENBL SELECT ENBL LLEN ENBL LEAD/LAG CHILLER ENABLE...
  • Page 38 Table 12 — Dual Chiller Configuration (Slave Chiller Example) SUB-MODE ITEM KEYPAD ENTRY DISPLAY ITEM EXPANSION COMMENTS DISP UNIT OPT1 CTRL CONTROL METHOD ENTER DEFAULT 0 OPT2 CTRL SWITCH (SEE NOTE 1) OPT2 ESCAPE CCNA CCNA CCN ADDRESS SCROLLING STOPS ENTER VALUE FLASHES ENTER...
  • Page 39 Table 13 — 4 to 20 mA Reset KEYPAD ITEM SUB-MODE ITEM DISPLAY COMMENT ENTRY EXPANSION 0 = no reset 1 = 4 to 20 mA input COOLING RESET 2 = Outdoor air temp CRST ENTER TYPE 3 = Return Fluid RSET 4 = Space Temperature 5.0 F...
  • Page 40 Table 15 — Configuring Outdoor Air and Space Temperature Reset DISPLAY MODE KEYPAD SUB- KEYPAD ITEM ITEM COMMENT Outdoor (RED LED) ENTRY MODE ENTRY EXPANSION Space DISP ENTER UNIT OPT1 OPT2 EXV.A EXV.B CONFIGURATION 2 = Outdoor-Air Temperature COOLING RESET RSET CRST 4 = Space Temperature...
  • Page 41: Demand Limit

    Under normal operation, the chiller will maintain a constant leaving fluid temperature approximately equal to the chilled fluid set point. As the cooler load varies, the entering cooler fluid will change in proportion to the load as shown in Fig. 27. Usually the chiller size and leaving-fluid temperature set point are selected based on a full-load condition.
  • Page 42: Demand Limit (Ccn Loadshed Controlled)

    DEMAND LIMIT (CCN Loadshed Controlled) — To con- Redline command is received, the current stage of capacity is figure Demand Limit for CCN Loadshed control set the De- set to the maximum stages available. Should the loadshed con-   mand Limit Select (Configuration RSET DMDC) to 3.
  • Page 43: Digital Scroll Option

    See Oil Charge section on system is varied by varying the time the compressor operates page 50 for Carrier approved oils. in an unloaded and loaded state during a 15-second period. If 6. Electrical power source must agree with unit nameplate.
  • Page 44: Check Refrigerant Charge

       CSP.1) or (Set Points COOL CSP.2), or if reset is Charge Adjustment for Brine Operation —  used, with the control point (Run Status VIEW For 30RAP010-060 units, the 30RAP chiller does not require a  CTPT). medium temperature brine modification at any temperature within the chiller application range which is as low as 14 F 6.
  • Page 45: Low Ambient Operation

    Contact position. When the unit receives a call for cooling (either from your Carrier representative for applicable LCWT range for the internal control or CCN network command or remote con- standard water-cooled chiller in a specific application.
  • Page 46: Service

    For all units, if temperature reset is being used, the unit con- controls the position of the electronic expansion valve stepper trols to a higher leaving-fluid temperature as the building load motor to maintain superheat set point. reduces. If demand limit is used, the unit may temporarily be The MBB controls the superheat leaving cooler to approxi- unable to maintain the desired leaving-fluid temperature be- mately 9°...
  • Page 47: Exv Valve Replacement

    1. Cable 2. Glass Seal 3. Motor Housing 4. Stepper Motor 5. Bearing 6. Lead Screw 7. Insert 8. Valve Piston 9. Valve Seat 10. Valve Port Fig. 30 — Cutaway View of the Electronic Expansion Valve (Size 070-150 Shown) FIELD SERVICING INSTRUCTIONS —...
  • Page 48: Valve Motor Replacement

    from the motor prior to installation. For 025, 030, 050- 060 sizes, replacement motors are shipped in the retracted position and may be installed as received; therefore, this step may be skipped if installing a new motor. CAUTION If the existing motor has been removed for inspection or cleaning, be sure that the piston is fully retracted into the motor assembly before installation on the valve.
  • Page 49 INCLUDED IN CABLE KIT CABLE CABLE CABLE RETAINER MOTOR AND ADAPTER MOTOR ADAPTER CABLE ASSEMBLY ASSEMBLY RETAINER GASKET MOTOR ADAPTER ASSEMBLY SIGHTGLASS SPORLAN FLOW NORMAL a30-4971 DIRECTION FLOW DIRECTION Fig. 32 — Electronic Expansion Valve Details (010-060) DISASSEMBLY CLOSED ADAPTER 27mm / 1 OPEN NOTE: Open valve in Quick Test sub-mode before disassembling.
  • Page 50: Compressor Replacement

    Puron refrigerant systems use a polyol ester (POE) oil. Use Compressor Power 24 to 28 in.-lb (2.7- to 3.2 N-m) only Carrier-approved compressor oil. Oil should be visible in Connections compressor oil sight glass. An acceptable oil level is from Compressor Ground 14 to 18 in.-lb (1.6 to 2.0 N-m)
  • Page 51: Microchannel Heat Exchanger (Mchx) Condenser Coil Maintenance And Cleaning

    UNIT SIZES 100-150 the core face. Reduce pressure and use caution to prevent damage to air centers. MANUFACTURER ICI......Emkarate RL 32H CAUTION Do not reuse drained oil or any oil that has been exposed to the atmosphere.
  • Page 52 SUCTION RGT SPT ACCESS VALVE DISCHARGE ACCESS VALVE a30-4974 SIGHT GLASS LEGEND — Discharge Pressure Thermostat — Discharge Temperature Thermistor DISCHARGE — Entering Water Thermistor ACCESS — High Pressure Switch FLOW — Leaving Water Thermistor VALVE SWITCH — Return Gas Thermistor —...
  • Page 53: Check Unit Safeties

    Insulate thermocouple to or otherwise negatively impact the Carrier warranty. avoid ambient temperatures from influencing reading. Temperature measured by thermocouple and temperature...
  • Page 54: Pressure Transducers

    value read by the control in the Temperatures mode using the scrolling marquee display. RGTA The suction and discharge Pressure Transducers — transducers are different part numbers and can be distinguished RGTB by the color of the transducer body, suction (yellow) and dis- charge (red).
  • Page 55 Table 25 — 5K Thermistor Temperatures (°F) vs. Resistance/Voltage Drop (Voltage Drop for EWT, LWT, RGT, and OAT) VOLTAGE VOLTAGE VOLTAGE TEMP RESISTANCE TEMP RESISTANCE TEMP RESISTANCE DROP DROP DROP (Ohms) (Ohms) (Ohms) 1.982 7,686 0.511 1,190 –25 3.699 98,010 1.956 7,665 0.502...
  • Page 56 Table 26 — 5K Thermistor Temperatures (°C) vs. Resistance/Voltage Drop (Voltage Drop for EWT, LWT, RGT, and OAT) VOLTAGE VOLTAGE VOLTAGE TEMP RESISTANCE TEMP RESISTANCE TEMP RESISTANCE DROP DROP DROP (Ohms) (Ohms) (Ohms) 1.982 7,855 0.506 1,158 –32 3.705 100,260 1.935 7,499 0.490...
  • Page 57 Table 27 — 10K Thermistor Temperature (°F) vs. Resistance/Voltage Drop (For SPT) VOLTAGE VOLTAGE VOLTAGE TEMP RESISTANCE TEMP RESISTANCE TEMP RESISTANCE DROP DROP DROP (Ohms) (Ohms) (Ohms) –25 4.758 196,453 2.994 14,925 0.890 2,166 –24 4.750 189,692 2.963 14,549 0.876 2,124 –23 4.741...
  • Page 58 Table 28 — 10K Thermistor Temperature (°C) vs. Resistance/Voltage Drop (For SPT) VOLTAGE VOLTAGE VOLTAGE TEMP RESISTANCE TEMP RESISTANCE TEMP RESISTANCE DROP DROP DROP (Ohms) (Ohms) (Ohms) –32 4.762 200,510 3.056 15,714 0.940 2,315 –31 4.748 188,340 3.000 15,000 0.913 2,235 –30 4.733...
  • Page 59: Strainer

    The flow sensor cable is provided with (3) LEDs that indi- step in the motor shaft. For proper performance, fan should be cate if 24 vac power is present and also status of the switch positioned such that it is securely seated on this step. Apply re- contacts.
  • Page 60: Drive Programming

    25 (+) and 2 (-). One addition- VFD. al jumper is required to configure the drive for 50/60 Hz opera- LOSS OF CCN COMMUNICATIONS — Carrier Comfort tion and input voltage. See Table 31 for proper inputs. Once the Network ®...
  • Page 61 LOW AMBIENT OPERATION (MOTORMASTER V) FIOP/ACCESSORY MM-A BLK-1 OFM1 BLK-2 BLK-3 GRN/YEL HIGH SCCR ONLY * MM SIGNAL CONNECTION VOLTAGE 208/230/460/575 1/4W FROM AUX-J4 BLK-1 OFM2 BLK-2 BLK-3 GRN/YEL COOLER/PUMP COOLER/PUMP HEATERS HEATERS (380,460,575V) (208/230,230V) a30-4977 LEGEND CONFIGURATION TABLE AUX — Auxiliary CONTROL INPUT —...
  • Page 62 Table 30 — Fault Codes FAULT CODE DESCRIPTION SOLUTION High Temperature Fault: Ambient temperature is too high; Check cooling fan operation Cooling fan has failed (if equipped). Control Fault: A blank EPM, or an EPM with corrupted data Perform a factory reset using Parameter 48 — has been installed.
  • Page 63 MODE 7 MODE 8 Line Voltage: 01 = low line, 02 = high line Carrier Freq: 01 = 4 kHz, 02 = 6 kHz, 03 = 8 kHz Startup mode: flying restart Stop mode: coast to stop Standard Speed source: 01= keypad,...
  • Page 64: Hydronic Package

    WARNING size available for that pump. The pump was selected based on the flow and head requirements as provided to Carrier. It is not Electrical shock can cause personal injury and death. Shut uncommon for actual pump duty to be different than what was off all power to this equipment during installation.
  • Page 65: Maintenance

    30 degree angle. The nozzle must be at least 12 in. from MAINTENANCE the core face. Reduce pressure and use caution to prevent The fol- Recommended Maintenance Schedule — damage to air centers. lowing are only recommended guidelines. Jobsite conditions may dictate that maintenance schedule is performed more often CAUTION than recommended.
  • Page 66: Motor Overload Protection

    If there is a command for a compressor to run and there is runs unloaded, the longer it must cool before the bi-metal disk no current, then one of the following safeties or conditions resets. See Fig. 44 for approximate reset times. have turned the compressor off: To manually reset ASTP, the compressor should be stopped Compressor Overcurrent —...
  • Page 67: Alarms And Alerts

    2. Check the thermistor protection chain located in the com- NOTE: Turning off power to the module will reset it immedi- pressor as follows: ately. a. De-energize control circuit and module power. b. Remove the sensor leads from the module (S1 and CAUTION S2).
  • Page 68 until the sub-menu item RCRN “RESET password, 1111. Press for each character. If the pass- ENTER ENTER ALL CURRENT ALARMS” is displayed. Press word has been changed, use the arrow keys to change each in- ENTER The control will prompt the user for a password, by displaying dividual character.
  • Page 69: Alarm/Alert Codes Table

    Table 34 — Alarm and Alert Codes ALARM/ ALARM WHY WAS THIS ACTION TAKEN RESET PROBABLE ALERT DESCRIPTION ALARM BY CONTROL METHOD CAUSE CODE ALERT GENERATED? High-pressure switch open, faulty CSB, loss of condenser Circuit A, Compressor 1 Compressor feedback signal Compressor A1 shut T051 Alert...
  • Page 70 Table 34 — Alarm and Alert Codes (cont) ALARM/ ALARM WHY WAS THIS ACTION TAKEN RESET PROBABLE ALERT DESCRIPTION ALARM BY CONTROL METHOD CAUSE CODE ALERT GENERATED? Temperature reset disabled. Chiller runs Outside Air Thermistor Thermistor outside range of under normal control/set Thermistor failure, damaged T073 Alert...
  • Page 71 Table 34 — Alarm and Alert Codes (cont) ALARM/ ALARM WHY WAS THIS ACTION TAKEN RESET PROBABLE ALERT DESCRIPTION ALARM BY CONTROL METHOD CAUSE CODE ALERT GENERATED? Automatic, only after first 3 daily Faulty transducer/ occurrences. Man- restricted condenser Circuit B High Compressor operation out- T127 Alert...
  • Page 72 Table 34 — Alarm and Alert Codes (cont) ALARM/ ALARM WHY WAS THIS ACTION TAKEN RESET PROBABLE ALERT DESCRIPTION ALARM BY CONTROL METHOD CAUSE CODE ALERT GENERATED? Pump 1 Auxiliary Contacts Cooler Pump 1 Aux Pump 1 turned off. Wiring error, faulty did not close within T190 Alert...
  • Page 73 LEGEND — Carrier Comfort Network — Current Sensor Board — Chillervisor System Manager — Current Sensor Board EEPROM — Electronic Erasable Programmable Read Only Memory — Energy Management Module — Entering Fluid Temperature —...
  • Page 74: Compressor Failure Alerts

    COMPRESSOR FAILURE ALERTS In addition, if a compressor stuck failure occurs and the cur- rent sensor board reports the compressor and the request off, T051, T052, T053 (Circuit A Compressor Failures) certain diagnostics will take place as follows: T055, T056, T057 (Circuit B Compressor Failures) — Alert 1.
  • Page 75 the alert is usually a faulty transducer, faulty 5-v power supply, 8 seconds, or the suction pressure is below 23 psig (158.6 kPa). or a loose connection. The cause of this alert may be low refrigerant charge, plugged liquid line filter drier, or sticking EXV. Check head pressure T092 (Circuit A Suction Pressure Transducer Failure) operation.
  • Page 76 T170 (Loss of Communication with the Compressor Expan- Cooler Flow/Interlock Contacts Opened During Normal Oper- sion Module) —This alert indicates that there are communica- ation Alarm. tions problems with the compressor expansion module. All When this alarm occurs, the chiller will be shut down. The functions performed by the CXB will stop.
  • Page 77: Appendix A - Display Tables

    APPENDIX A — DISPLAY TABLES Run Status Mode and Sub-Mode Directory SUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENT AUTO VIEW OF RUN STATUS xxx.x °F Entering Fluid Temp xxx.x °F Leaving Fluid Temp SETP xxx.x °F Active Set Point CTPT xxx.x °F Control Point LOD.F Load/Unload Factor...
  • Page 78 APPENDIX A — DISPLAY TABLES (cont) Run Status Mode and Sub-Mode Directory (cont) SUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENT PREVENTIVE MAINTENANCE PUMP PUMP MAINTENANCE SI.PM xxxx HRS Pump Service Interval Default: 8760 P.1.DN xxxx HRS Pump 1 Service Countdown P.2.DN xxxx HRS Pump 2 Service Countdown P.1.MN...
  • Page 79 APPENDIX A — DISPLAY TABLES (cont) Service Test Mode and Sub-Mode Directory SUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENT* To enable Service Test mode, move Enable/Off/Remote contact switch to TEST Service Test Mode OFF. Change TEST to ON. Move switch to ENABLE OUTPUTS EXV.A xxx%...
  • Page 80 APPENDIX A — DISPLAY TABLES (cont) Pressures Mode and Sub-Mode Directory SUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENT PRESSURES CIRCUIT A PRC.A DP.A xxx.x PSIG Discharge Pressure SP.A xxx.x PSIG Suction Pressure PRESSURES CIRCUIT B PRC.B DP.B xxx.x PSIG Discharge Pressure See Note SP.B xxx.x PSIG...
  • Page 81 APPENDIX A — DISPLAY TABLES (cont) Outputs Mode and Sub-Mode Directory SUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENT GENERAL OUTPUTS FAN1 ON/OFF Fan 1 Relay FAN2 ON/OFF Fan 2 Relay FAN3 ON/OFF Fan 3 Relay FAN4 ON/OFF Fan 4 Relay FAN5 ON/OFF Fan 5 Relay FAN6...
  • Page 82 APPENDIX A — DISPLAY TABLES (cont) Configuration Mode and Sub-Mode Directory SUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENT DISPLAY CONFIGURATION TEST ON/OFF Test Display LEDs METR ON/OFF Metric Display Off = English On = Metric Default: 0 0 = English DISP LANG Language Selection 1 = Espanol...
  • Page 83 APPENDIX A — DISPLAY TABLES (cont) Configuration Mode and Sub-Mode Directory (cont) SUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENT UNIT OPTIONS 2 CONTROLS Default: 0 0 = Enable/Off/Remote Switch CTRL Control Method 2 = Occupancy 3 = CCN Control Default: 1 LOAD Loading Sequence Select 1 = Equal...
  • Page 84 APPENDIX A — DISPLAY TABLES (cont) Configuration Mode and Sub-Mode Directory (cont) SUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENT CIR A EXV CONFIGURATION Default:25% EXV Opening at Low LWT EXV.L Range:0 to 50% Default:10 F XX° F LWT for EXV Min Opening LWT.L Range:-20 to 40 F Default:50%...
  • Page 85 APPENDIX A — DISPLAY TABLES (cont) Configuration Mode and Sub-Mode Directory (cont) SUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENT MOTORMASTER MMR.S YES/NO Motormaster Select Default: No Default: 1 P.GAN Head Pressure P Gain Range: 1 to 4 Default: 0.1 I.GAN XX.X Head Pressure I Gain Range: -20 to 20 Default: 0.0...
  • Page 86 APPENDIX A — DISPLAY TABLES (cont) Configuration Mode and Sub-Mode Directory (cont) SUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENT SETPOINT AND RAMP LOAD Default: 0 0 = Single 1 = Dual Switch CLSP Cooling Set Point Select 2 = Dual CCN Occupied 3 = 4 to 20 mA Input (requires EMM) SLCT...
  • Page 87 APPENDIX A — DISPLAY TABLES (cont) Time Clock Mode and Sub-Mode Directory SUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENT TIME OF DAY TIME HH.MM XX.XX Hour and Minute Military (00:00 - 23:59) MONTH, DATE, DAY, AND YEAR 1 - 12 (1 = January, MNTH Month of Year 2 = February, etc.)
  • Page 88 APPENDIX A — DISPLAY TABLES (cont) Time Clock Mode and Sub-Mode Directory (cont) SUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENT HOLIDAY SCHEDULE 09 1 - 12 (1 = January, Holiday Start Month 2 = February, etc.) HD.09 Start Day 01-31 Duration (days) HOLIDAY SCHEDULE 10 1 - 12 (1 = January, Holiday Start Month...
  • Page 89 APPENDIX A — DISPLAY TABLES (cont) Time Clock Mode and Sub-Mode Directory (cont) SUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENT HOLIDAY SCHEDULE 20 1 - 12 (1 = January, Holiday Start Month 2 = February, etc.) HD.20 Start Day 01-31 Duration (days) HOLIDAY SCHEDULE 21 1 - 12 (1 = January, Holiday Start Month...
  • Page 90 APPENDIX A — DISPLAY TABLES (cont) Time Clock Mode and Sub-Mode Directory (cont) SUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENT SCH.N Schedule Number 0 SCH.L LOCAL OCCUPANCY SCHEDULE OCCUPANCY PERIOD 1 OCC.1 XX:XX Period Occupied Time Military (00:00 - 23:59) UNC.1 XX:XX Period Unoccupied Time Military (00:00 - 23:59)
  • Page 91 APPENDIX A — DISPLAY TABLES (cont) Time Clock Mode and Sub-Mode Directory (cont) SUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENT OCCUPANCY PERIOD 6 OCC.6 XX:XX Period Occupied Time Military (00:00 - 23:59) UNC.6 XX:XX Period Unoccupied Time Military (00:00 - 23:59) MON.6 YES/NO Monday In Period...
  • Page 92 APPENDIX A — DISPLAY TABLES (cont) Operating Mode and Sub-Mode Directory SUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENT MODES CONTROLLING UNIT MD01 ON/OFF CSM Controlling Chiller MD02 ON/OFF WSM Controlling Chiller MD03 ON/OFF Master/Slave Control MD05 ON/OFF Ramp Load Limited MD06 ON/OFF Timed Override in effect MD07...
  • Page 93: Appendix B - Ccn Tables

    APPENDIX B — CCN TABLES CCN DISPLAY TABLES — A_UNIT (General Unit Parameters) DESCRIPTION VALUE UNITS POINT NAME FORCIBLE Control Mode 0 = Test STAT 1 = Local Off 2 = CCN Off 3 = Clock Off 4 = Emergency Stop 5 = Local On 6 = CCN On 7 = Clock On...
  • Page 94 APPENDIX B — CCN TABLES (cont) CCN DISPLAY TABLES — CIRCADIO (Circuit A Discrete Inputs/Outputs) DESCRIPTION VALUE UNITS POINT NAME FORCIBLE CIRC. A DISCRETE OUTPUTS Compressor A1 Relay On/Off K_A1_RLY Compressor A2 Relay On/Off K_A2_RLY Compressor A3 Relay On/Off K_A3_RLY Minimum Load Valve Relay On/Off MLV_RLY...
  • Page 95 APPENDIX B — CCN TABLES (cont) CCN DISPLAY TABLES — OPTIONS (Unit Parameters) DESCRIPTION VALUE UNITS POINT NAME FORCIBLE FANS Fan 1 Relay Off/On FAN_1 Fan 2 Relay Off/On FAN_2 Fan 3 Relay Off/On FAN_3 Fan 4 Relay Off/On FAN_4 Fan 5 Relay Off/On FAN_5...
  • Page 96 APPENDIX B — CCN TABLES (cont) CCN CONFIGURATION TABLES — OPTIONS1 (Options 1 Configuration) DESCRIPTION VALUE DEFAULT UNITS POINT NAME Cooler Fluid 1 = Water FLUIDTYP 2 = Med. Brine Minimum Load Vlv Select No/Yes MLV_FLG CSB Board Enable Dsable/Enable Enable CSB_ENA Cooler Pump Control...
  • Page 97 APPENDIX B — CCN TABLES (cont) CCN CONFIGURATION TABLES — RESETCON (Temperature Reset and Demand Limit) DESCRIPTION VALUE DEFAULT UNITS POINT NAME COOLING RESET Cooling Reset Type 0 = No Reset CRST_TYP 1 = 4-20 mA input 2 = External temp – OAT 3 = Return Fluid 4 = External temp - SPT 4-20 MA RESET...
  • Page 98 APPENDIX B — CCN TABLES (cont) CCN CONFIGURATION TABLES — DISPLAY (Marquee Display SETUP) DESCRIPTION VALUE DEFAULT UNITS POINT NAME Service Password nnnn 1111 PASSWORD Password Enable Enable/Disable Enable PASS_EBL Metric Display Off/On DISPUNIT Language Selection 0 = ENGLISH LANGUAGE 1 = FRANCAIS 2 = ESPANOL 3 = PORTUGUES...
  • Page 99 APPENDIX B — CCN TABLES (cont) CCN SERVICE TABLES — SERVICE DESCRIPTION VALUE DEFAULT UNITS POINT NAME SERVICE F Brine Freeze Point nnn.n 34.0 BRN_FRZ Pump Service Interval nnnnn 876.0 hours SI_PUMPS COMPRESSOR ENABLE Enable Compressor A1 Disable/Enable Dependent on unit size ENABLEA1 Enable Compressor A2 Disable/Enable...
  • Page 100 APPENDIX B — CCN TABLES (cont) CCN MAINTENANCE TABLES — STRTHOUR DESCRIPTION VALUE UNITS POINT NAME Machine Operating Hours nnnnnn hours HR_MACH Machine Starts nnnnnn CY_MACH Circuit A Run Hours nnnnnn hours HR_CIRA Compressor A1 Run Hours nnnnnn hours HR_A1 Compressor A2 Run Hours nnnnnn hours...
  • Page 101 APPENDIX B — CCN TABLES (cont) CCN MAINTENANCE TABLES — ALARMS DESCRIPTION VALUE POINT NAME Active Alarm #1 Axxx or Txxx ALARM01C Active Alarm #2 Axxx or Txxx ALARM02C Active Alarm #3 Axxx or Txxx ALARM03C Active Alarm #4 Axxx or Txxx ALARM04C Active Alarm #5 Axxx or Txxx...
  • Page 102 APPENDIX B — CCN TABLES (cont) CCN MAINTENANCE TABLES — PM-PUMP DESCRIPTION VALUE UNITS POINT NAME Pump Service Interval nnnnnn hours SI_PUMPS Pump 1 Service Countdown nnnnnn hours P1_CDOWN Pump 1 Maintenance Done Yes/No P1_MAINT Pump 2 Service Countdown nnnnnn hours P2_CDOWN Pump 2 Maintenance Done...
  • Page 103 APPENDIX B — CCN TABLES (cont) CCN MAINTENANCE TABLES — TESTMODE DESCRIPTION VALUE UNITS POINT NAME Service Test Mode On/Off NET_CTRL Compressor A1 Relay On/Off S_A1_RLY Compressor A2 Relay On/Off S_A2_RLY Compressor A3 Relay On/Off S_A3_RLY Compressor A4 Relay On/Off S_A4_RLY Compressor B1 Relay On/Off...
  • Page 104 APPENDIX B — CCN TABLES (cont) CCN MAINTENANCE TABLES — RUNTEST (cont) DESCRIPTION VALUE UNITS POINT NAME Minimum Load Valve Relay On/Off MLV_RLY Compressor B1 Feedback On/Off K_B1_FBK Compressor B2 Feedback On/Off K_B2_FBK Compressor B3 Feedback On/Off K_B3_FBK Fan 1 Relay On/Off FAN_1 Fan 2 Relay...
  • Page 105 APPENDIX B — CCN TABLES (cont) CCN MAINTENANCE TABLES — DUALCHIL DESCRIPTION VALUE UNITS POINT NAME Dual Chiller Link Good? Yes/No DC_LINK Master Chiller Role Stand Alone, Lead Chiller, MC_ROLE Lag Chiller Slave Chiller Role Stand Alone, Lead Chiller, SC_ROLE Lag Chiller F Lead Chiller Ctrl Point...
  • Page 106: Appendix C - Factory Settings For Pump And Manual Starters

    APPENDIX C — FACTORY SETTINGS FOR PUMP AND MANUAL STARTERS 30RAP UNIT SIZE PUMP SIZE PUMP OPTION* UNIT VOLTAGE OVERLOAD SETTING 208/230-60 380-60 1.5 HP 2, 9 460-60 575-60 208/230-60 380-60 3 HP 3, 4, B, C 460-60 575-60 208/230-60 14.5 380-60 010-060...
  • Page 107: Option

    APPENDIX D — BACNET COMMUNICATIONS OPTION The following section is used to configure the UPC Open con- troller which is used when the BACnet* communications option is selected. The UPC Open controller is mounted in the 10's main control box per unit components arrangement diagrams. TO ADDRESS THE UPC OPEN CONTROLLER —...
  • Page 108 The example in Fig. C shows the BAS Port DIP Switches set for 76.8k (Carrier default) and MS/TP. due to echoing. See Fig. A, D, and E. Set the BAS Port DIP Switches DS2 and DS1 for the appro-...
  • Page 109 APPENDIX D — BACNET COMMUNICATIONS OPTION (cont) Fig. E — BT485 Terminator Installation To install a BT485 terminator, push the BT485 terminator temperature rating specifications list two acceptable alterna- on to the BT485 connector located near the BACnet connector. tives. The Halar specification has a higher temperature rating and a tougher outer jacket than the SmokeGard specification, NOTE: The BT485 terminator has no polarity associated with and it is appropriate for use in applications where the user is...
  • Page 110 APPENDIX D — BACNET COMMUNICATIONS OPTION (cont) Table D — Open System Wiring Specifications and Recommended Vendors WIRING SPECIFICATIONS RECOMMENDED VENDORS AND PART NUMBERS Connect Air Contractors Wire Type Description Belden RMCORP International Wire and Cable 22 AWG, single twisted shielded pair, low capacitance, CL2P, TC foam FEP, plenum rated.
  • Page 111 10,000 hours of data retention during power out- Open defaults to CCN Acknowledger. If a Chiller Lead/Lag/ ages. Standby application is being used, then the Carrier technician IMPORTANT: Power must be ON to the UPC Open when must change the configuration to only one CCN Acknowledger replacing the battery, or the date, time, and trend data will on the CCN bus.
  • Page 112 APPENDIX D — BACNET COMMUNICATIONS OPTION (cont) Table G — Network Points List CCN POINT READ/ DEFAULT BACNET BACNET POINT DESCRIPTION UNITS RANGE NAME WRITE VALUE OBJECT ID OBJECT NAME 4-20 ma Demand Signal LMT_MA AV:36 lmt_ma_1 4-20 ma Reset Signal RST_MA °F AV:33...
  • Page 113 APPENDIX D — BACNET COMMUNICATIONS OPTION (cont) Table G — Network Points List (cont) CCN POINT READ/ DEFAULT BACNET BACNET POINT DESCRIPTION UNITS RANGE NAME WRITE VALUE OBJECT ID OBJECT NAME 1 = Test 2 = Local Off 3 = CCN Off 4 = Clock Off 5 = Emergency Stop Control Mode...
  • Page 114 APPENDIX D — BACNET COMMUNICATIONS OPTION (cont) Table G — Network Points List (cont) READ/ DEFAULT BACNET BACNET POINT DESCRIPTION POINT NAME UNITS RANGE WRITE VALUE OBJECT ID OBJECT NAME Fan Relay 1 FAN_1 BV:60 fan_1_1 Fan Relay 2 FAN_2 BV:61 fan_2_1 Fan Relay 3...
  • Page 115: Option

    APPENDIX D — BACNET COMMUNICATIONS OPTION (cont) Table G — Network Points List (cont) READ/ DEFAULT BACNET BACNET POINT DESCRIPTION POINT NAME UNITS RANGE WRITE VALUE OBJECT ID OBJECT NAME Saturated Condensing Tmp TMP_SCTA °F AV:16 tmp_scta_1 Saturated Condensing Tmp TMP_SCTB °F AV:25...
  • Page 116: Appendix E - Maintenance Summary And Log Sheets

    APPENDIX E — MAINTENANCE SUMMARY AND LOG SHEETS 30RAP Weekly Maintenance Log Plant ___________________________ Machine Model No. ________________ CHECK ALARMS OPERATOR DATE OIL LEVEL REMARKS / FAULTS INITIALS NOTE: Equipment failures caused by lack of adherence to the Main- tenance Interval Requirements are not covered under warranty.
  • Page 117 APPENDIX E — MAINTENANCE SUMMARY AND LOG SHEETS (cont) 30RAP Monthly Maintenance Log Month Date Operator UNIT SECTION ACTION UNIT ENTRY Check Oil Level yes/no Compressor Leak Test yes/no Inspect and Clean Cooler yes/no Every 3 - 5 Years Inspect Cooler Heater amps Cooler Leak Test...
  • Page 118 APPENDIX E — MAINTENANCE SUMMARY AND LOG SHEETS (cont) 30RAP Seasonal Shutdown Log Month Date Operator UNIT SECTION ACTION ENTRY Isolate and Drain Cooler Cooler Add Glycol for Freeze Protection Controls Do Not Disconnect Control Power NOTE: Equipment failures caused by lack of adherence to the Maintenance Interval Requirements are not covered under warranty.
  • Page 119: Index

    29, 30, 59 Replacement Valve motor replacement, EXV Heat exchanger Capacity control Valve replacement, EXV Brazed plate cooler heat exchanger Capacity control overrides Voltage Carrier Comfort Network ® (CCN) Winter shutdown MCHX condenser coil 51, 65 interface Heater cable CCN tables...
  • Page 120: Manufacturer Reserves The Right To Discontinue, Or Change At Any Time, Specifications Or Designs Without Notice And Without Incurring Obligations

    Copyright 2012 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53300097-01 Printed in U.S.A. Form 30RAP-4T Pg 120 7-12 Replaces: 30RAP-3T...
  • Page 121: Start-Up Checklist For 30Rap Liquid Chiller

    START-UP CHECKLIST FOR 30RAP LIQUID CHILLER (Remove and use for Job File) I. Project Information JOB NAME ______________________________________________________________________________ ADDRESS _______________________________________________________________________________ CITY ____________________________________________ STATE _______________ ZIP______________ INSTALLING CONTRACTOR ________________________________________________________________ SALES OFFICE ___________________________________________________________________________ START-UP PERFORMED BY ________________________________________________________________ Design Information CAPACITY CEAT FLUID TYPE FLOW RATE P.D.
  • Page 122   6. CHILLED WATER PUMP STARTER INTERLOCKED WITH CHILLER.   7. CHILLED WATER FLOW SWITCH IS OPERATIONAL.   8. WATER LOOP VOLUME GREATER THAN MINIMUM REQUIREMENTS. (See Table 20).   9. PROPER LOOP FREEZE PROTECTION PROVIDED TO _____ °F (°C). ANTIFREEZE TYPE _____________________ CONCENTRATION __________%.
  • Page 123 OPERATING DATA: RECORD THE FOLLOWING INFORMATION FROM THE PRESSURES AND TEMPERATURES MODES WHEN MACHINE IS IN A STABLE OPERATING CONDITION: PRESSURE/TEMPERATURE CIRCUIT A CIRCUIT B DISCHARGE PRESSURE DP.A DP.B SUCTION PRESSURE SP.A SP.B SATURATED CONDENSING TEMP SCT.A SCT.B SATURATED SUCTION TEMP SST.A SST.B RETURN GAS TEMPERATURE...
  • Page 124 CONDENSER FAN MOTOR CURRENT FAN MOTOR 1 FAN MOTOR 2 FAN MOTOR 3 FAN MOTOR 4 FAN MOTOR 5 FAN MOTOR 6 FAN MOTOR 7 FAN MOTOR 8 FAN MOTOR 9 FAN MOTOR 10 COOLER PUMP MOTOR CURRENT COOLER PUMP 1 COOLER PUMP 2 Record Software Versions MODE —...
  • Page 125 III. Unit Start-Up (cont) RECORD CONFIGURATION SETTINGS UNIT (Configuration Settings) SUBMODE ITEM ITEM EXPANSION DISPLAY ENTRY UNIT CONFIGURATION SIZE UNIT SIZE SZA.1 COMPRESSOR A1 SIZE SZA.2 COMPRESSOR A2 SIZE SZA.3 COMPRESSOR A3 SIZE SZB.1 COMPRESSOR B1 SIZE UNIT SZB.2 COMPRESSOR B2 SIZE SZB.3 COMPRESSOR B3 SIZE XX.X F...
  • Page 126 III. Unit Start-Up (cont) PRESS ESCAPE KEY TO DISPLAY ‘OPT1’. PRESS DOWN ARROW KEY TO DISPLAY ‘OPT2’. PRESS ENTER KEY. RECORD CONFIGURATION INFORMATION BELOW. OPTIONS2 (Options Configuration) SUBMODE ITEM ITEM EXPANSION DISPLAY ENTRY UNIT OPTIONS 2 CONTROLS CTRL CONTROL METHOD LOAD LOADING SEQUENCE SELECT LLCS...
  • Page 127 III. Unit Start-Up (cont) PRESS ESCAPE KEY TO DISPLAY ‘HP.B’. PRESS DOWN ARROW KEY TO DISPLAY ‘EXV.A’. PRESS ENTER KEY. RECORD CONFIGURATION INFORMATION BELOW. EXV.A (Circuit A EXV Configuration) SUB-MODE ITEM ITEM EXPANSION DISPLAY ENTRY EXV OPENING AT LOW LWT EXV.L LWT FOR EXV MIN OPENING XX°...
  • Page 128 III. Unit Start-Up (cont) PRESS ESCAPE KEY TO DISPLAY ‘EXV.B’. PRESS DOWN ARROW KEY TO DISPLAY ‘MM’. PRESS ENTER KEY. RECORD CONFIGURATION INFORMATION BELOW. MM (Motormaster Configuration Settings) SUB-MODE ITEM ITEM EXPANSION DISPLAY ENTRY MMR.S MOTORMASTER SELECT YES/NO P.GAN HEAD PRESSURE P GAIN I.GAN HEAD PRESSURE I GAIN XX.X...
  • Page 129 III. Unit Start-Up (cont) PRESS ESCAPE KEY TO DISPLAY ‘RSET’. PRESS DOWN ARROW KEY TO DISPLAY ‘SLCT’. PRESS ENTER KEY. RECORD CONFIGURATION INFORMATION BELOW: SLCT (Setpoint and Ramp Load Configuration) SUBMODE ITEM ITEM EXPANSION DISPLAY ENTRY SETPOINT AND RAMP LOAD CLSP COOLING SETPOINT SELECT RL.S...
  • Page 130 III. Unit Start-Up (cont) COMPONENT TEST USE ESCAPE/ARROW KEYS TO ILLUMINATE CONFIGURATION LED. PRESS ENTER TO DISPLAY ‘DISP’. PRESS ENTER AGAIN TO DISPLAY ‘TEST’ FOLLOWED BY ‘OFF’. PRESS ENTER TO STOP DISPLAY AT ‘OFF’ AND ENTER AGAIN SO ‘OFF’ DISPLAY FLASHES. ‘PASS’ AND ‘WORD’ WILL FLASH IF PASSWORD NEEDS TO BE ENTERED.
  • Page 131 Service Test Mode and Sub-Mode Directory (cont) KEYPAD ITEM Completed SUB-MODE ITEM DISPLAY COMMENT ENTRY EXPANSION (Yes/No) CIRCUIT A COMPRESSOR TEST CC.A1 ON/OFF COMPRESSOR A1 RELAY ENTER DIG.P 0 to 15 COMP A1 UNLOAD PERCENT Digital Scroll option only CMPA CC.A2 ON/OFF COMPRESSOR A2 RELAY...
  • Page 132: Manufacturer Reserves The Right To Discontinue, Or Change At Any Time, Specifications Or Designs Without Notice And Without Incurring Obligations

    TECHNICIAN _____________________________ REPRESENTATIVE _____________________________ DATE ___________________________________ DATE ________________________________________ Copyright 2012 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53300097-01 Printed in U.S.A. Form 30RAP-4T...

Table of Contents