Carrier Ecologic Series 3 Controls, Start-Up, Operation, Service, And Troubleshooting page 40

Air-cooled and fluid cooled chillers. 50/60 hz
Table of Contents

Advertisement

SUBFUNCTION
1 Ice Build Schedule*
2 Local Schedule†
3 Remote Schedule
(Currently Not
Used)
4 Holiday Configuration**
5-33 Holiday Configuration
*Ice configuration select must be set to 1 for clock control. The ice configuration can be accessed by pressing
†Clock control select must be set to 1 for clock control. The clock control can be accessed by pressing
**The BROADCAST function (BRODEFS table) must be activated (change to "YES" and download) when using the Remote Enhanced Display controller, Building
Supervisor or ComfortWorks® software for the control to recognize holidays.
Table 27 — Schedule Function and Subfunction Directory
KEYPAD ENTRY
ENTER
ENTER
through
DISPLAY
SCHEDULES: OCCPC01S
Timed Override: 00
SCHEDULES: OCCPC01S
Timed Override: 02
MTWTFSSH OCC UNOCC
01- 00000000 00:00 00:00
MTWTFSSH OCC UNOCC
ENTER
01- 11111000 00:00 00:00
MTWTFSSH OCC UNOCC
ENTER
01-11111000 21:00 00:00
MTWTFSSH OCC UNOCC
ENTER
01-11111000 21:00 06:30
MTWTFSSH OCC UNOCC
02- 00000000 00:00 00:00
SCHEDULES: OCCPC02S
Timed Override: 00
MTWTFSSH OCC UNOCC
01- 00000000 00:00 00:00
MTWTFSSH OCC UNOCC
ENTER
01- 11111000 00:00 00:00
MTWTFSSH OCC UNOCC
ENTER
01-11111000 06:30 00:00
MTWTFSSH OCC UNOCC
ENTER
01-11111000 06:30 21:00
MTWTFSSH OCC UNOCC
02- 00000000 00:00 00:00
SCHEDULES: OCCPC65S
Timed Override: 00
MTWTFSSH OCC UNOCC
01- 00000000 00:00 00:00
MTWTFSSH OCC UNOCC
ENTER
01- 11111000 00:00 00:00
MTWTFSSH OCC UNOCC
ENTER
01-11111000 06:30 00:00
MTWTFSSH OCC UNOCC
ENTER
01-11111000 06:30 21:00
MTWTFSSH OCC UNOCC
02- 00000000 00:00 00:00
HOLIDAYS: HOLDY_01
Starts on 00/00 00 days
HOLIDAYS: HOLDY_01
ENTER
Starts on 12/23 00 days
HOLIDAYS: HOLDY_01
Starts on 12/23 10 days
HOLIDAYS: HOLDY_02
Starts on 00/00 00 days
40
COMMENT
Extended Occupied Time
Two hour override entered
Displays current stored schedule
(First two numbers are schedule, 01-08)
Monday-Friday now occupied
Occupied time now set
Unoccupied time now set
Ice Build schedule completed
Can enter up to 7
additional ice build schedules
Extended Occupied Time
Displays current stored schedule
(First two numbers are schedule, 01-08)
Monday-Friday now occupied
Occupied time now set
Unoccupied time now set
Local schedule completed
Can enter up to 7
additional local schedules
Extended Occupied Time
Displays current stored schedule
(First two numbers are schedule, 01-08)
Monday-Friday now occupied
Occupied time now set
Unoccupied time now set
Remote schedule completed
Can enter up to 7
additional remote schedules
Can configure holiday start day
and duration
Start of holiday set
Holiday duration set
Allows configuration of 29
additional holiday periods
and scrolling down.
and scrolling down.