Carrier Ecologic Series 3 Controls, Start-Up, Operation, Service, And Troubleshooting page 48

Air-cooled and fluid cooled chillers. 50/60 hz
Table of Contents

Advertisement

ALARM/ALERT
ALARM OR
CODE
ALERT
31
Alert
32
Alarm
34
Alert
35
Alert
36
Alarm
37
Alert
38
Alert
40
Alert
41
Alert
42
Alert
43
Alert
44
Alarm
45
Alarm
46
Alarm
Table 36 — Alarm and Alert Codes (cont)
WHY WAS THIS
DESCRIPTION
ALARM GENERATED?
Circuit B Economizer
Calibration offset more
Transducer Failure
than 6 PSIG (41 kPa) or
Voltage ratio (volts read/
ref. voltage) more than
99.9% or less than 0.5%
Transducer Supply Out-
Reference voltage mea-
side 4.5 to 5.5 Volts
sured at PSIO-1, J7-
34,35 less than 4.5 V or
greater than 5.5 V.
4-20 mA Reset Input Out
If configured and input
of Range
signal to PSIO-2,
J7-19,20(HX),
J7-22,23(GX) less than
2 mA or greater than
20mA
4-20 mA Demand Limit
If configured and input
Input Out of Range
signal to PSIO-2,
J7-22,23(HX),
J7-13,14(GX) less than
2 mA or greater than
20mA
Loss of Communication
PSIO-1 has lost commu-
with "Hardware Point"
nication with one of the
points in Table 37.
Circuit A Low
SST reads 6 F (3.3 C) or
Saturated Suction
more below the brine
Temperature
freeze point for 3 min-
utes. For brines, SST
may also be 14 F (7.8 C)
or more below the lowest
cooling set point.
Circuit B Low
SST reads 6 F (3.3 C) or
Saturated Suction
more below the brine
Temperature
freeze point for 3 min-
utes. For brines, SST
may also be 14 F (7.8 C)
or more below the lowest
cooling set point.
Compressor A1 Low Oil
See Note 1.
Pressure
Compressor A2 Low Oil
See Note 1.
Pressure
Compressor B1 Low Oil
See Note 1.
Pressure
Compressor B2 Low Oil
See Note 1.
Pressure
Circuit A Condenser
For W/C chillers only, if
Freeze Protection (alarm
SCT < 34 F (1.1 C)
ignored for brine chillers)
Circuit B Condenser
For W/C chillers only, if
Freeze Protection (alarm
SCT < 34 F (1.1 C)
ignored for brine chillers)
Cooler Freeze
Cooler EWT or LWT less
Protection
than freeze point. Freeze
point is 34 F (1.1 C) for
water, cooling set point
minus 8 F (4.4 C) for
brines.
ACTION TAKEN
BY CONTROL
Circuit B shut down
Chiller shut down
Reset function disabled.
Normal set point used
Demand limit ignored.
Runs under normal con-
trol based on 100%
demand limit.
See Table 37.
Circuit A shut down
Circuit B shut down
Comp A1 shut down
Comp A2 shut down
Comp B1 shut down
Comp B2 shut down
Chiller shut down. Turn
Cond. pump On if Chiller
is Off
Chiller shut down. Turn
Cond. pump On if Chiller
is Off
Chiller shut down.
Leave Cooler pump on.
Turn Cooler pump On if
Chiller is Off.
48
PROBABLE
RESET METHOD
CAUSE
Automatic
Transducer failure, power
supply failure, or wiring
damage/error.
Automatic
Power supply failure or
wiring error. Low trans-
former voltage.
Automatic
Faulty signal generator,
wiring error, 500 ohm
resistor missing or not
properly installed.
Automatic
Faulty signal generator,
wiring error, 500 ohm
resistor missing or not
properly installed.
Automatic
Failed module, wiring
error, failed transformer,
loose connection plug,
wrong address
Manual
Low refrigerant charge,
plugged strainer, faulty
expansion valve. Low
water flow.
Manual
Low refrigerant charge,
plugged strainer, faulty
expansion valve. Low
water flow.
Manual
Low Water Temperature,
low refrigerant charge,
plugged oil filter, closed
oil valve, bad oil solenoid,
compressor oil check
valve stuck, oil line check
valve stuck, plugged oil
strainer
Manual
Low Water Temperature,
low refrigerant charge,
plugged oil filter, closed
oil valve, bad oil solenoid,
compressor oil check
valve stuck, oil line check
valve stuck, plugged oil
strainer
Manual
Low Water Temperature,
low refrigerant charge,
plugged oil filter, closed
oil valve, bad oil solenoid,
compressor oil check
valve stuck, oil line check
valve stuck, plugged oil
strainer
Manual
Low Water Temperature,
low refrigerant charge,
plugged oil filter, closed oil
valve, bad oil solenoid,
compressor oil check
valve stuck, oil line check
valve stuck, plugged oil
strainer
Automatic
Failed/bad discharge
pressure transducer,
refrigerant leak,
configured for water-
cooled condenser
Automatic
Failed/bad discharge
pressure transducer,
refrigerant leak,
configured for water-
cooled condenser
Automatic**
Faulty thermistor, low
water flow