Carrier Ecologic Series 3 Controls, Start-Up, Operation, Service, And Troubleshooting page 33

Air-cooled and fluid cooled chillers. 50/60 hz
Table of Contents

Advertisement

SUBFUNCTION
KEYPAD ENTRY
1 Service Configuration
2 Options Configuration 1
3 Options Configuration 2
See Legend on page 36.
Table 22 — Service Function and Subfunction Directory
DISPLAY
Software CESR_500100 Ver
xxx
Unit Type
x
Number of Cir A Comp
x
Compressor A1 Tonnage
xx
Compressor A2 Tonnage
xx
Cap. High Temp Override
x
Number of Cir B Comp
x
Compressor B1 Tonnage
xx
Compressor B2 Tonnage
xx
Max. Cond. Temp Setpoint
xxx.x dF
MOP Setpoint
xx.x dF
Fan Staging Select
x
CPM Board Used?
Yes
Compr. A1 Must Trip Amps
xxx.x
Compr. A2 Must Trip Amps
xxx.x
Compr. B1 Must Trip Amps
xxx.x
Compr. B2 Must Trip Amps
xxx.x
Cooler Fluid Select
x
Min. Load Valve Select
x
Loading Sequence Select
x
Lead/Lag Sequence Select
x
Head Press. Control Type
x
Motormaster Select
x
Water Valve Type
x
Ext. Reset Sensor Select
x
Cooler Pump Interlock
x
Cooler Pump Control
x
Condenser Pump Control
x
Condenser Flow Switch
x
Condenser Water Sensors
x
Heat Reclaim Sensors
x
Cooling Setpoint Select
x
Heating Setpoint Select
x
1 = Air-cooled (30GX), 2 = Water-cooled (30HXC)
3 = Split system (30HXA)
30GX = 154 F (68 C)
30HXA = 152 F (67 C)
30HXC = 122 F (50 C)
Default = 52 F (11.1 C)
Displays "Not Used" or a number.
See Table 7 (30GX only).
Value from CPM module. See Appendix A.
Value from CPM module. See Appendix A.
Value from CPM module. See Appendix A.
Value from CPM module. See Appendix A.
1 = Water (Default), 2 = Medium Temp Brine
3 = Low Temp Brine (HX only)
Displays Enable/Dsable
Default: Dsable
1 = Equal circuit, 2 = Staged circuit
Default: 2. See page 7.
1 = Automatic (Default), 2 = Circuit A leads,
3 = Circuit B leads
0 = None (Default, HX), 1 = Air cooled (Default, for GX and must be set to 1 for
HXA control of remote A/C condenser fans), 2 = Water cooled (HXC only)
0 = None (Default), 1 = Direct control
0 = None (Default), 1 = 4-20 mA, 2 = 2-10 V
3 = 20-4 mA, 4 = 10-2 V
0 = Space Temp Thermistor (Default)
1 = Outside Air Themistor
0 = No interlock
1 = Interlock enabled (Default)
0 = Not controlled (Default)
1 = On/Off control
0 = Not controlled (Default, and 30HXA control of remote A/C condenser fans)
1 = On/Off control
2 = Off when stages equal 0 (unit off)
Displays Enable/Dsable
Default: Dsable
0 = Not used (Default)
1 = Used
CURRENTLY NOT SUPPORTED
0 = Single set point (Default), 1 = Dual set point
(switch controlled), 2 = Dual set point (clock controlled)
0 = Single set point (Default), 1 = Dual set point
(switch controlled), 2 = Dual set point (clock controlled)
CURRENTLY NOT SUPPORTED